TP系列無環流靜止式進相器是襄陽(yang)拓邦電(dian)(dian)(dian)(dian)(dian)氣自(zi)選研制(zhi)開發的(de)新一代高(gao)(gao)新技術(shu)產品,是一種專(zhuan)為大中型(xing)繞線(xian)式異步(bu)電(dian)(dian)(dian)(dian)(dian)動機(ji)設計制(zhi)作的(de)就地無功(gong)(gong)功(gong)(gong)率補(bu)償(chang)裝置。它串(chuan)接于(yu)電(dian)(dian)(dian)(dian)(dian)機(ji)轉(zhuan)子(zi)(zi)回(hui)路,改(gai)變(bian)轉(zhuan)子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)流(liu)與(yu)轉(zhuan)子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)壓(ya)(ya)的(de)相位(wei)關系(xi),通過(guo)磁場進而改(gai)變(bian)電(dian)(dian)(dian)(dian)(dian)機(ji)定子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)流(liu)與(yu)電(dian)(dian)(dian)(dian)(dian)壓(ya)(ya)的(de)相位(wei)關系(xi),達到提高(gao)(gao)電(dian)(dian)(dian)(dian)(dian)機(ji)自(zi)身功(gong)(gong)率因數、降(jiang)低(di)電(dian)(dian)(dian)(dian)(dian)機(ji)定子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)流(liu)和溫(wen)升的(de)目(mu)的(de)。這種方式從根本(ben)上改(gai)善了電(dian)(dian)(dian)(dian)(dian)機(ji)的(de)運行(xing)狀況,顯著降(jiang)低(di)電(dian)(dian)(dian)(dian)(dian)機(ji)及電(dian)(dian)(dian)(dian)(dian)網(wang)的(de)無功(gong)(gong)損耗,對節能(neng)降(jiang)耗、降(jiang)低(di)單位(wei)產品成(cheng)本(ben),提高(gao)(gao)企(qi)業的(de)經濟效益(yi)具有重(zhong)要(yao)的(de)意義。


TP系列無環流靜止式進相器(qi)對(dui)無功(gong)(gong)功(gong)(gong)率的(de)補(bu)償(chang)與電(dian)(dian)(dian)機(ji)定子側并聯電(dian)(dian)(dian)容器(qi)的(de)補(bu)償(chang)有著本(ben)質的(de)區別。電(dian)(dian)(dian)容補(bu)償(chang)只是在電(dian)(dian)(dian)機(ji)之外的(de)電(dian)(dian)(dian)網上(shang)對(dui)無功(gong)(gong)進行(xing)補(bu)償(chang),減(jian)少(shao)電(dian)(dian)(dian)網的(de)無功(gong)(gong)輸(shu)入,電(dian)(dian)(dian)網的(de)功(gong)(gong)率因(yin)數得到提高(gao),但是電(dian)(dian)(dian)機(ji)的(de)無功(gong)(gong)消耗并沒有減(jian)少(shao),無法改善電(dian)(dian)(dian)機(ji)本(ben)身的(de)運行(xing)狀況;而TP系列靜止式進相器是串接在電(dian)(dian)機(ji)轉子回路(lu)中(zhong),不僅可顯著提高(gao)功率(lv)因數,使電(dian)(dian)機(ji)定子電(dian)(dian)流大幅度降低,而且電(dian)(dian)機(ji)溫升明顯降低,電(dian)(dian)機(ji)的效率(lv)和過載能力顯著提高(gao)。

TP系列靜止式(shi)進(jin)相(xiang)(xiang)(xiang)器與自(zi)激(ji)(旋轉)式(shi)進(jin)相(xiang)(xiang)(xiang)機(ji)(ji)也不(bu)同。TP系列靜止式(shi)進(jin)相(xiang)(xiang)(xiang)器采用(yong)了 的(de)(de)交(jiao)-交(jiao)變頻技術和(he)微機(ji)(ji)、可控硅控制技術,可自(zi)動跟蹤電(dian)機(ji)(ji)運行狀態的(de)(de)變化并(bing)自(zi)動調整相(xiang)(xiang)(xiang)關參(can)數以達到(dao)佳的(de)(de)補(bu)償效果,這是自(zi)激(ji)式(shi)進(jin)相(xiang)(xiang)(xiang)機(ji)(ji)無法做到(dao)的(de)(de)。而(er)且,TP系列靜止式(shi)進(jin)相(xiang)(xiang)(xiang)器從根本(ben)上克(ke)服了自(zi)激(ji)式(shi)進(jin)相(xiang)(xiang)(xiang)機(ji)(ji)“整流子”結構特別怕塵埃、壽命(ming)短(duan)、維修頻繁的(de)(de)缺點;具有參(can)數調節容(rong)易(yi)、主回路無轉動部件、不(bu)怕灰塵、可靠性高(gao)、使(shi)用(yong)壽命(ming)長、維護方便,是理想(xiang)的(de)(de)取代自(zi)激(ji)式(shi)進(jin)相(xiang)(xiang)(xiang)機(ji)(ji)的(de)(de)新型高(gao)科技產(chan)品。

TP系列靜(jing)止式進(jin)相(xiang)器可(ke)廣泛用于水泥(ni)、化工、礦山、冶(ye)金、鋼鐵(tie)、造紙、制藥等行業(ye)的(de)大中型(xing)高低壓(ya)繞線式異步(bu)電機。


二型號命名

TP系列靜止式進相器型號命名方法如下:





型號:TP-800,表示適(shi)用于(yu)額(e)定(ding)轉子電流不超(chao)過800A的電機(ji)的靜(jing)止式進相器。


三工作原理

當電(dian)(dian)(dian)機(ji)運行進(jin)(jin)相(xiang)(xiang)時(shi),進(jin)(jin)相(xiang)(xiang)器(qi)(qi)通(tong)過(guo)轉(zhuan)(zhuan)子(zi)電(dian)(dian)(dian)流(liu)傳(chuan)感器(qi)(qi)采集到(dao)(dao)的轉(zhuan)(zhuan)子(zi)電(dian)(dian)(dian)流(liu)信號(hao)及工頻電(dian)(dian)(dian)壓提供的同步信號(hao)經微處理(li)器(qi)(qi)CPU進(jin)(jin)行數(shu)據和(he)相(xiang)(xiang)位處理(li),控(kong)制可控(kong)硅(gui)的觸(chu)發信號(hao),調整由12只晶閘管組成的交—交變頻裝(zhuang)置,將降壓后的工頻電(dian)(dian)(dian)源變為和(he)轉(zhuan)(zhuan)子(zi)電(dian)(dian)(dian)流(liu)同頻率,相(xiang)(xiang)位滯后90°的附加(jia)電(dian)(dian)(dian)勢加(jia)在(zai)電(dian)(dian)(dian)機(ji)轉(zhuan)(zhuan)子(zi)回路中。轉(zhuan)(zhuan)子(zi)的電(dian)(dian)(dian)流(liu)和(he)電(dian)(dian)(dian)壓相(xiang)(xiang)位因(yin)此改變,通(tong)過(guo)磁場(chang)進(jin)(jin)而(er)改變電(dian)(dian)(dian)機(ji)定(ding)子(zi)電(dian)(dian)(dian)流(liu)與定(ding)子(zi)電(dian)(dian)(dian)壓的相(xiang)(xiang)位角,使電(dian)(dian)(dian)機(ji)的功率因(yin)數(shu)提高,得到(dao)(dao)補(bu)償(chang)。

當電(dian)機在某一負載下運行時(shi),其轉子電(dian)流為I2e、定子電(dian)流為I1e, 向量圖如(ru)下所示(shi)。







從(cong)電機學我們知道,激(ji)磁電流Im由(you)關系式(shi)Im=I1e-I2e,從(cong)向(xiang)量圖(tu)可(ke)得(de)出Im。當(dang)進相器的電勢疊(die)加在轉(zhuan)子(zi)回路后(hou),轉(zhuan)子(zi)電流的相位變為(wei)圖(tu)中的I2。由(you)于負載不(bu)變,激(ji)磁電流Im不(bu)變。此時的定子(zi)電流I1由(you)關系式(shi)I1=Im+I2從(cong)向(xiang)量圖(tu)可(ke)得(de)出I1,如圖(tu)所示。從(cong)圖(tu)中可(ke)以看(kan)出I1的功率因數角(jiao)和幅值(zhi)都比I1e小(xiao),說明電機的功率因數有所提(ti)高,定子(zi)電流有所下降。

進相(xiang)(xiang)器就是這樣改變轉(zhuan)子(zi)電(dian)流(liu)(liu)與轉(zhuan)子(zi)電(dian)壓的(de)相(xiang)(xiang)位(wei)關系,通(tong)過磁場進而改變電(dian)機(ji)定(ding)子(zi)電(dian)流(liu)(liu)與定(ding)子(zi)電(dian)壓的(de)相(xiang)(xiang)位(wei)關系,減小功率因(yin)數(shu)角(jiao),終使電(dian)機(ji)本身的(de)功率因(yin)數(shu)得(de)以(yi)提高,定(ding)子(zi)電(dian)流(liu)(liu)得(de)以(yi)下降,達到對電(dian)機(ji)補償的(de)目的(de)。

當負(fu)載(zai)發(fa)生改變時,微處理(li)器(qi)實時檢測(ce)電機參數的變化,并(bing)根據負(fu)載(zai)的變化,動態(tai)調整附加在(zai)轉子上的電勢幅值,以使(shi)電機的功率因(yin)數始(shi)終保持在(zai)期望(wang)值上。

四(si)原理框圖






電容式補償(chang)的矢量(liang)分析:








電容補償和進相(xiang)器補償的原理圖分別如下:






圖中,將(jiang)電(dian)(dian)機進行了等效簡化,R1、X1為電(dian)(dian)機定子等效電(dian)(dian)路的(de)電(dian)(dian)阻(zu)和電(dian)(dian)感,R2、X2為電(dian)(dian)機轉子等效電(dian)(dian)路的(de)電(dian)(dian)阻(zu)和電(dian)(dian)感,C為就地(di)補(bu)償的(de)電(dian)(dian)容,Uf為進相(xiang)器的(de)等效電(dian)(dian)路,M為電(dian)(dian)機的(de)接(jie)線點。

從圖可以看出,靜止(zhi)式進(jin)相(xiang)器和電(dian)(dian)容補償對電(dian)(dian)機(ji)的作用(yong)點不同,電(dian)(dian)容是在(zai)(zai)電(dian)(dian)機(ji)的前端(duan)(duan)定(ding)子(zi)側進(jin)行補償,其補償范圍(wei)是在(zai)(zai)補償點的前端(duan)(duan);靜止(zhi)式進(jin)相(xiang)器串聯在(zai)(zai)電(dian)(dian)機(ji)的后端(duan)(duan),其補償范圍(wei)擴大到了電(dian)(dian)機(ji)。

五性能特點

1、可使(shi)電機的功率因數提高到0.95以上,無功功率降低60%以上。

2、降(jiang)低定(ding)子電流10%-20%。

3、降低線損、銅損20%-30%。

4、電機溫升降低5%。

5、過載能力和(he)效率(lv)大大提高,電(dian)機使用壽命延長。

6、具有故障自(zi)動保(bao)護功能,保(bao)障設備長期安全運行。

7、操作(zuo)簡單(dan),安(an)裝調試(shi)和(he)維修保養(yang)均不影(ying)響正常(chang)生產(chan),半年(nian)內可收回成本。

六(liu)使用條件

1、安裝地點環(huan)境溫度(du)≤40℃

2、安裝地點相對濕度≤90%

3、 安裝地點無火災(zai)、爆炸危險品,無化學腐(fu)蝕及(ji)劇烈振動。

4、海拔高度≤1500M。

5、進相器(qi)柜(ju)體上方(fang)0.5米內應(ying)通風;如無地溝,須將(jiang)進相器(qi)柜(ju)體架(jia)空(kong)0.1米。

注:TP系列靜止式進相器應滿足上(shang)方要求(qiu)的使用(yong)條件,襄陽拓邦電氣還可提供(gong)適用于(yu)高原地區(海拔(ba)超過(guo)1500米)的靜止式進相器(但用(yong)戶須事先(xian)特別申請)。

七技術參數


相 器 型 號

配 電 機 參 數

額定轉子電流(A

額定功率(KW

TP-400

400

95-800

TP-500

400-500

245-1000

TP-600

500-600

315-1250

TP-800

600-800

630-1600

TP-1000

800-1000

1000-2000

TP-1200

1000-1200

1600-2500

TP-1500

1200-1500

2000以上




八安裝尺寸

1、外(wai)型尺寸圖






2、安裝基(ji)礎(chu)圖(tu)







3、規格尺寸表



型號

外形尺寸(MM)

安裝尺寸(MM)

(W)

(D)

(H)

(E)

(F)

螺孔

TP400-600

1000

760

2000

780

620

14

TP800-1000

1100

800

2000

880

650

14

TP1200-1500

1200

900

2200

980

750

16



注:隨著產品不斷更新(xin)換代,外(wai)形及安裝尺寸會(hui)有所變(bian)化,請以具體的產品為準。

九安裝調試

(一)安裝

1、將進相(xiang)器(qi)搬到(dao)安裝位(wei)置,注意進相(xiang)器(qi)柜體底部應與(yu)地溝相(xiang)通或架空,首先是(shi)打開柜子的前后門,從上(shang)到(dao)下(xia),逐一(yi)地擰緊螺絲,防(fang)止在運輸過程中螺絲松動(dong)造成(cheng)進相(xiang)器(qi)不能正常工作。

2、準(zhun)備好(hao)連接【主(zhu)電(dian)(dian)機轉子至進相器(qi)接觸器(qi)KM13的三根電(dian)(dian)纜】、【進相器(qi)接觸器(qi)KM11至主(zhu)電(dian)(dian)機起(qi)動柜的三根電(dian)(dian)纜】,其線徑應能承載(zai)主(zhu)電(dian)(dian)機轉子額定電(dian)(dian)流,比好(hao)長度并壓好(hao)接頭。

3、進相(xiang)(xiang)器(qi)上(shang)的電(dian)(dian)(dian)流(liu)表(biao)、功率(lv)因(yin)數(shu)表(biao)是直(zhi)接(jie)從電(dian)(dian)(dian)機(ji)定(ding)子(zi)回(hui)路(lu)上(shang)的電(dian)(dian)(dian)流(liu)互(hu)感(gan)(gan)器(qi)、電(dian)(dian)(dian)壓(ya)(ya)(ya)互(hu)感(gan)(gan)器(qi)取信(xin)號(hao),要求(qiu)所(suo)用電(dian)(dian)(dian)流(liu)互(hu)感(gan)(gan)器(qi)副邊的額(e)定(ding)電(dian)(dian)(dian)流(liu)為(wei)(wei)5A、電(dian)(dian)(dian)壓(ya)(ya)(ya)互(hu)感(gan)(gan)器(qi)副邊的額(e)定(ding)電(dian)(dian)(dian)壓(ya)(ya)(ya)為(wei)(wei)100V,若用戶現用的不滿足該(gai)要求(qiu),則(ze)須另行準(zhun)備(bei)符合上(shang)述要求(qiu)的互(hu)感(gan)(gan)器(qi)。(注:電(dian)(dian)(dian)壓(ya)(ya)(ya)互(hu)感(gan)(gan)器(qi)僅適用于高壓(ya)(ya)(ya)電(dian)(dian)(dian)機(ji),對低(di)壓(ya)(ya)(ya)電(dian)(dian)(dian)機(ji),進相(xiang)(xiang)器(qi)電(dian)(dian)(dian)壓(ya)(ya)(ya)信(xin)號(hao)直(zhi)接(jie)從定(ding)子(zi)回(hui)路(lu)取)

4、新(xin)電(dian)機(ji)(ji)須(xu)帶(dai)上(shang)90%以上(shang)負載并正常運轉后才可調試(shi)進相器,用戶在通知我(wo)方(fang)調試(shi)前,應調試(shi)好電(dian)機(ji)(ji)、減速(su)機(ji)(ji)、磨機(ji)(ji)等(deng)其它(ta)設備,使其帶(dai)上(shang)負載正常運轉,以免延誤(wu)進相器調試(shi)時間。

5、各聯鎖線意義如下:

(225、227)取自電(dian)機起(qi)(qi)動(dong)柜星(xing)點(dian)短接接觸(chu)器(qi)的輔助常開(kai)點(dian),只有在(zai)電(dian)機起(qi)(qi)動(dong)完畢后,進(jin)(jin)相器(qi)才可以進(jin)(jin)相。

(355、357)當開關柜主(zhu)開關是(shi)接觸器時與(yu)分閘按(an)鈕(niu)并聯(lian);是(shi)斷路器時與(yu)分閘按(an)鈕(niu)串聯(lian), 進相狀態下主(zhu)電機(ji)(ji)(ji)不(bu)能(neng)停機(ji)(ji)(ji),只有先退相才能(neng)停主(zhu)機(ji)(ji)(ji)。

(359、361)串入開關柜合閘(zha)回(hui)路。當(dang)KM11吸合時(shi),可(ke)以起動電機。

(363、369)從起動柜控(kong)(kong)制(zhi)電源(yuan)引單相380V,使KM11與起動柜控(kong)(kong)制(zhi)回路同時(shi)得電。

(30、32)串入(ru)主電(dian)(dian)(dian)機電(dian)(dian)(dian)流(liu)(liu)計(ji)量回(hui)路(lu);(40、42)并(bing)入(ru)主電(dian)(dian)(dian)機電(dian)(dian)(dian)壓計(ji)量回(hui)路(lu)。(取(qu)A相(xiang)(xiang)(xiang)電(dian)(dian)(dian)流(liu)(liu)則取(qu)B,C相(xiang)(xiang)(xiang)電(dian)(dian)(dian)壓,如此類推,電(dian)(dian)(dian)流(liu)(liu)和電(dian)(dian)(dian)壓不得取(qu)同(tong)相(xiang)(xiang)(xiang))。

(A、B、C、N)接三相四線電源,導線橫(heng)截(jie)面(mian)積:TP600以下(xia)用(yong)(yong)4mm2;TP1000以下(xia)用(yong)(yong)6mm2;TP1500以下(xia)用(yong)(yong)10mm2。

6、控制器所有指示燈的含義說明如(ru)下:

(1)主板(ban)(中(zhong)間一塊)的指示(shi)燈(從上往下數)

●L1、L2、L3:電(dian)機(ji)(ji)轉子三相電(dian)流信號指示(shi)(電(dian)機(ji)(ji)運轉時為循(xun)環顯示(shi)狀(zhuang)態(tai);自(zi)檢試驗時為隨機(ji)(ji)狀(zhuang)態(tai):或亮(liang)、或滅)

●L4:+5V電源(yuan)指示(shi)(保持亮的(de)狀態)

●L5:熱故(gu)障(zhang)指示(有熱故(gu)障(zhang)時L5滅)

●L6:缺(que)相及(ji)自動故(gu)障保(bao)護(hu)指示(有缺(que)相故(gu)障及(ji)其它故(gu)障時L6燈(deng)滅)

●L7:+15V電源(yuan)指示(保持亮的狀態(tai))

●L8:-15V電源(yuan)指示(保持亮(liang)的狀態)

(2)驅動板(兩(liang)邊兩(liang)塊)

●分別代表(biao)12個可控制硅的(de)觸發(fa)信號(指(zhi)示燈均亮,并有(you)規律的(de)閃(shan)爍)

(二)試驗

1、檢查(cha)主電纜、聯鎖(suo)線(xian)、儀表線(xian)連(lian)接是否正確。

2、檢(jian)查各器件螺絲是否緊固。

3、用(yong)萬(wan)用(yong)表測量可控硅極間電阻:

●觸發極(ji)G與陰極(ji)K間(jian)電阻為幾(ji)十(shi)歐(ou)姆;

●觸發極(ji)G與(yu)陽極(ji)A間電阻(zu)大于幾十千歐;

●陰(yin)極(ji)K與陽極(ji)A間電阻大于幾十(shi)千歐;

●陰極K與(yu)陽極A用萬用表200K檔測(ce)量,阻值應從小(xiao)變化(hua)到無(wu)限(xian)大(da)。

4、合上(shang)起動柜電(dian)源,進相(xiang)器(qi)背面的接觸(chu)器(qi)KM11應吸合,短接225、227;合上(shang)進相(xiang)器(qi)電(dian)源,電(dian)源指示燈(deng)亮(liang);控(kong)制(zhi)器(qi)應有電(dian),控(kong)制(zhi)器(qi)上(shang)指示燈(deng)亮(liang)。

5、控制器上(shang)撥碼開關(guan)打在ON(上(shang)方(fang))位置,中(zhong)間主板L1、L2、L3循環亮或(huo)滅,L4~L8全亮;兩邊兩塊(kuai)驅動板指示燈閃爍。

6、按(an)綠(lv)色進相(xiang)(xiang)按(an)鈕(niu),進相(xiang)(xiang)器(qi)(qi)(qi)前面(mian)的(de)接(jie)觸器(qi)(qi)(qi)KM13吸合,延時后(hou),背面(mian)的(de)接(jie)觸器(qi)(qi)(qi)KM11斷開,綠(lv)色進相(xiang)(xiang)指示燈亮,風(feng)機運轉(zhuan),風(feng)應向上吹,主變(bian)壓器(qi)(qi)(qi)副(fu)邊電流不超過30A,并(bing)且沒(mei)有大(da)幅度變(bian)化。

7、按紅(hong)色退相(xiang)按鈕,進相(xiang)器(qi)后面的(de)接(jie)觸器(qi)KM11吸(xi)合,延時后,前面的(de)接(jie)觸器(qi)KM13斷開,綠(lv)色進相(xiang)指(zhi)示(shi)燈滅,紅(hong)色電源指(zhi)示(shi)燈亮,進相(xiang)器(qi)即退出進相(xiang)狀態。

8、通(tong)電試(shi)驗結束,請務必斷開225、227。

(三)調試(shi)

1、運行(xing)前:控制器(qi)主板上撥碼開關(guan)應打在OFF(下方(fang))位(wei)置。

2、起(qi)動(dong)主電(dian)(dian)機(ji):打(da)開(kai)進(jin)相器前(qian)柜門,合上(shang)空氣開(kai)關,進(jin)相器電(dian)(dian)源接(jie)通,面板上(shang)的紅色電(dian)(dian)源指(zhi)示(shi)燈亮(liang),關閉(bi)柜門,等(deng)待主機(ji)起(qi)動(dong)。

3、進(jin)相(xiang):(1)電機正常運轉(zhuan)后,按綠色(se)進(jin)相(xiang)按鈕,進(jin)相(xiang)器前面(mian)(mian)的(de)接(jie)觸器KM13吸合(he),延時后,背面(mian)(mian)的(de)接(jie)觸器KM11斷開,綠色(se)進(jin)相(xiang)指示(shi)燈(deng)亮,風(feng)機運轉(zhuan),定子電流(liu)應下(xia)降,功率因數(shu)應上(shang)升(sheng)(sheng)。如果定子電流(liu)不(bu)下(xia)降反而(er)上(shang)升(sheng)(sheng),調(diao)整同步變壓器上(shang)6V、6V0兩線(xian)的(de)位置,再進(jin)相(xiang)。

(2)測量主變壓(ya)器原(yuan)、副邊(bian)電流,應無大(da)幅度擺動(dong)。

(3)電(dian)機定子電(dian)流應平穩,無(wu)大幅(fu)度擺(bai)動。

(4)六(liu)個電(dian)抗器上(shang)端銅排的電(dian)流擺動幅度應一致。

4、退(tui)相(xiang):按(an)紅色(se)(se)退(tui)相(xiang)按(an)鈕,進相(xiang)器(qi)(qi)后(hou)面的接(jie)觸器(qi)(qi)KM11吸合,延時后(hou),前面的接(jie)觸器(qi)(qi)KM13斷開,綠色(se)(se)進相(xiang)指示燈(deng)滅,紅色(se)(se)電源指示燈(deng)亮,進相(xiang)器(qi)(qi)即退(tui)出(chu)進相(xiang)狀態。

5、停(ting)車(che):進相器退相后,按(an)下主(zhu)機停(ting)車(che)按(an)鈕,電(dian)機即停(ting)車(che)。

(四)測量和(he)觀(guan)察(cha)

1、測量可(ke)控硅(gui)、銅排(pai)、交流接(jie)觸器、電(dian)抗(kang)器、主變壓器、控制板溫度。

2、測量可(ke)控硅(gui)觸發電壓;主變壓器一次、二次電流(liu)(liu);電抗器輸入電流(liu)(liu)。

3、觀察風機運行情況。

4、觀察整體運(yun)行(xing)情(qing)況(kuang),有無異常響聲或銅排有無大(da)的抖動(dong)現象等。

十使用維護

為確保TP系列靜止式進相器長期安全、可(ke)靠(kao)地運行,請操作人員特別(bie)注意以下(xia)事(shi)項:

1、嚴禁在進相器運行期間,切(qie)斷進相器外部(bu)電源(yuan)。

2、定期檢查冷(leng)卻風機運轉(zhuan)狀況,冷(leng)卻風機停轉(zhuan)使可(ke)控(kong)硅(gui)散熱能力下降,可(ke)能燒壞可(ke)控(kong)硅(gui)。

3、定期檢(jian)測主變壓器原、副(fu)邊(bian)運行電流。

4、定(ding)期檢(jian)測可(ke)控(kong)硅、聯接(jie)銅排、交流接(jie)觸器(qi)、電(dian)抗(kang)器(qi)、主變(bian)壓(ya)器(qi)、控(kong)制(zhi)板(ban)的溫度。

5、定期檢(jian)修(xiu)主回路接觸器(qi)的觸頭。真空(kong)接觸器(qi)定期檢(jian)測(ce)絕(jue)緣電阻,用(yong)(yong)5KV或2.5KV搖表檢(jian)查,當開關管(guan)絕(jue)緣電阻小于100兆(zhao)歐時,應(ying)加強監視,小于20兆(zhao)歐時應(ying)立即更換新(xin)管(guan),以延(yan)長接觸器(qi)的使(shi)用(yong)(yong)壽命,保障進相器(qi)及電機安全(quan)運(yun)行。

6、當(dang)進相器停用(yong)一段時間又重(zhong)新啟用(yong)時, 次進相前應觀察(cha)柜內控制單元上各指(zhi)示燈是否正常。電機起(qi)動并正常運轉(zhuan)后,各指(zhi)示燈顯示如(ru)下:

·主板(ban)(中間一塊):除(chu)L1,L2,L3周(zhou)期性循環顯示外(注意:此指電機在(zai)運轉時(shi)的狀(zhuang)態,若電機未轉,該三燈為(wei)隨(sui)機狀(zhuang)態),其它各(ge)燈均亮(liang)。

·驅動扳(ban)(兩邊(bian)的兩塊):其上面各指示燈均亮(liang)并有輕微(wei)閃(shan)爍。

7、當電機定子(zi)電流出(chu)現異常大幅(fu)擺動時,應(ying)立即退相(xiang),查出(chu)原因(yin)并檢(jian)修后投入使用。

8、定期打掃柜內(nei)衛(wei)生(sheng)。

十一故(gu)障處理



主電機不能起動(dong)

端子363、369無380V 電源

檢(jian)查起動柜(ju)控制電源(yuan)

 

接觸器KM11不吸合

檢查KM11線包及其控制回路

 

接觸器KM11吸合,但其輔助觸點未閉合

檢修其輔助(zhu)觸點

 

端子359、361串入合閘回路的線未接通

檢查該(gai)回路(lu)

不能投入(ru)進相

空氣開關QF1、QF2、QF3沒合上

合上空氣開關

 

按鈕STP、ST接觸不良

 

 

中間繼電器KA11觸點接觸不良

 

 

主電機起動柜內星點接觸器常開輔助觸點不能閉合(225、227未接通)

檢修該(gai)接觸(chu)器輔助觸(chu)點及連線

 

KM13不(bu)能吸合

檢查KM13線包及其控制回路

 

固態繼電器FV損壞或者不導通

控制器主控制板L6燈滅

檢查主控板7腳對11、12、13腳有無+、-3伏左右電壓,否則更換電流傳感器

 

 

檢查固態繼電器FV

FV的3、4腳(jiao)有直流15V電壓(ya),而323、325不通,須更換該(gai)繼(ji)電器

進相后主電機停機

接入開關柜的KM11、KM13的輔助觸點359、361接觸不好

維(wei)修該觸(chu)點

 

進(jin)相(xiang)器投(tou)入(ru)進(jin)相(xiang)瞬(shun)間外(wai)部空氣開(kai)關(guan)跳閘

更(geng)換(huan)大(da)規格的空氣開關

進相后無效果(guo)

接入主控板的電流傳感器信號(hao)線錯(cuo)誤

電流傳感器從左到右TA1、TA2、TA3的信號線應分別對應與主控板的13、12、11腳

 

主控板(ban)的(de)撥碼開關在自檢位(wei)

撥碼開關(guan)撥至工作(zuo)位

 

KM13吸(xi)合后KM11未(wei)釋放(時(shi)間(jian)繼電器KT11壞)

更換KT11時間繼電器

 

KM15沒有吸(xi)合

KM11的輔助觸點(dian)301、305接(jie)觸不良

維修該觸(chu)點

 

 

KM15線(xian)圈故障

更換KM15線圈

 

KM15主觸點接觸不(bu)良

更換KM15

 

主(zhu)變壓器原邊(bian)開路(lu)

更換(huan)主變壓器

進(jin)相后主電(dian)機電(dian)流不減反增

同步電源(yuan)相序(xu)錯誤

調換進相器內小變壓器TC上輸出6V、6V0電壓的兩線位置

 

電機轉速下降(缺相(xiang)),自動退相(xiang)

KM13主觸點(dian)接觸不良

維修該觸點

 

 

電機轉子線松動(dong),進相(xiang)時的電流沖擊導致缺相(xiang)

檢查電(dian)機轉子線

進(jin)相后主電(dian)機電(dian)流擺(bai)動(dong)大

可控硅擊穿

測量可控硅極間電阻(詳細方法見調試(shi)部分)

 

觸(chu)發板損壞

測量可控硅控制極與陰極之間應有0.2V以上的直流電壓信號,否則應檢查觸發板

 

主板的撥(bo)碼開關在(zai)自檢位

撥(bo)碼開(kai)關(guan)撥(bo)至工作(zuo)位

 

電機轉子線松動

檢(jian)查電機轉子線

 

KM13采用節能型線圈時,線圈故障導致KM13進行瞬間來回釋放、吸合,導致主回路接觸不良

維修或更換KM13線圈





注意(yi):進相器檢修不得在進相(xiang)狀態下(xia)進行,發現問題應立即退相(xiang)。

十二控制(zhi)板(ban)檢修



現象

原因

對(dui)策(ce)

L1L2L3不循環閃爍,L6滅,其它各燈正常

轉(zhuan)子缺相(xiang)

檢查接觸器KM2主觸頭是否損壞,若損壞,則維修觸頭或更換接觸器

電流傳(chuan)感器器損壞

檢查電流傳感器是否有±2V以上的輸出信號,否則更換傳感器

主(zhu)控板元器件損壞

依次更換IC210IC211

L1L2L3不周期性閃爍,其它各燈正常

主控板元器件損(sun)壞

依次更換IC210IC211IC205IC207

L6滅,其它各燈正常

主控(kong)板元器(qi)件損壞

依次更換IC207IC209

L5滅,其它各燈正常

散熱器溫度檢測回路(lu)故障

檢查(cha)溫度開關及(ji)其連線

L4L7L8全部或部分滅

電源故障

1、檢查變壓器及控制板是否有±18V電源

2、更換相應的780578157915

F1-L1L6 F2-L1L6部分指示燈亮,主板各燈正常

觸發板元器件損壞

1、有一片ULN2004損壞,更換之

2、脈沖變壓器接觸不良,作相應處理

F1-L1L6 F2-L1L6指示燈全滅,主板各燈正常

觸發板(ban)元器件損壞(huai)

1、兩片ULN2004損壞,更換之

2、更換555芯片

觸發板無電源

1、檢查主板7815是否有虛焊

2、檢查觸發板19腳與主板6腳連接是否正常





十三(san)注意事項

1、進相器檢修應(ying)在退相狀(zhuang)態下進行(xing),發(fa)現問題應(ying)立即(ji)退相。

2、嚴禁隨意帶電插拔控制板,檢(jian)修控制板時,一定(ding)要(yao)把空(kong)開QF3打(da)下來。

3、更(geng)換可控硅(gui)時應注意陰、陽(yang)極(ji)的方向,并壓緊散熱器(壓力不要過大),裝上后(hou)擰(ning)緊所(suo)有螺絲(si),之后(hou)再(zai)(zai)檢(jian)測(ce)可控硅(gui)各極(ji)間(jian)的電阻情況(kuang)。若一(yi)只可控硅(gui)擊穿(chuan)在柜體上直接檢(jian)測(ce),同一(yi)相(xiang)的四個可控硅(gui)均(jun)顯示擊穿(chuan),此時應把該組可控硅(gui)間(jian)的聯接銅排(pai)拆掉(diao)再(zai)(zai)測(ce) 。

十四(si)訂貨須知

1、提供電(dian)機型(xing)號、額(e)定(ding)(ding)功率(lv)、定(ding)(ding)子電(dian)壓、定(ding)(ding)子電(dian)流、轉(zhuan)子電(dian)壓、轉(zhuan)子電(dian)流、額(e)定(ding)(ding)功率(lv)因數。

2、提供電機拖(tuo)動負載的特征及負載率。

預知TP系列無環流靜止式進相器的(de)更(geng)多信息,請撥(bo)打襄陽拓邦電(dian)氣官(guan)網電(dian)話: 鄭經理17771133316或咨詢網站客(ke)服(fu)!!