TP系列無環流靜止式進相器是(shi)(shi)襄陽拓(tuo)邦電(dian)(dian)氣(qi)自選研(yan)制開(kai)發的(de)新一(yi)代高新技(ji)術產品(pin),是(shi)(shi)一(yi)種(zhong)專為(wei)大中型繞(rao)線(xian)式異步電(dian)(dian)動機(ji)設(she)計制作的(de)就(jiu)地無(wu)功(gong)(gong)功(gong)(gong)率補償(chang)裝置。它(ta)串接于電(dian)(dian)機(ji)轉子回路,改(gai)變轉子電(dian)(dian)流(liu)(liu)與轉子電(dian)(dian)壓的(de)相(xiang)位(wei)關(guan)系,通過磁(ci)場進而改(gai)變電(dian)(dian)機(ji)定子電(dian)(dian)流(liu)(liu)與電(dian)(dian)壓的(de)相(xiang)位(wei)關(guan)系,達到提(ti)高電(dian)(dian)機(ji)自身功(gong)(gong)率因數、降低電(dian)(dian)機(ji)定子電(dian)(dian)流(liu)(liu)和(he)溫升(sheng)的(de)目的(de)。這種(zhong)方式從根(gen)本(ben)上改(gai)善(shan)了電(dian)(dian)機(ji)的(de)運行狀況(kuang),顯(xian)著(zhu)降低電(dian)(dian)機(ji)及電(dian)(dian)網的(de)無(wu)功(gong)(gong)損耗(hao),對節(jie)能降耗(hao)、降低單位(wei)產品(pin)成(cheng)本(ben),提(ti)高企業的(de)經濟效益具有重(zhong)要的(de)意(yi)義。
TP系(xi)列無環(huan)流(liu)靜止(zhi)式(shi)進相器(qi)對無功(gong)(gong)(gong)(gong)功(gong)(gong)(gong)(gong)率的(de)(de)補償(chang)與電(dian)機定(ding)子(zi)側并聯(lian)電(dian)容器(qi)的(de)(de)補償(chang)有著(zhu)本質的(de)(de)區(qu)別。電(dian)容補償(chang)只是(shi)在電(dian)機之外的(de)(de)電(dian)網上對無功(gong)(gong)(gong)(gong)進行補償(chang),減少電(dian)網的(de)(de)無功(gong)(gong)(gong)(gong)輸入,電(dian)網的(de)(de)功(gong)(gong)(gong)(gong)率因數得到提(ti)高,但是(shi)電(dian)機的(de)(de)無功(gong)(gong)(gong)(gong)消耗并沒有減少,無法改善電(dian)機本身的(de)(de)運行狀況;而(er)TP系列靜止式進相器是串(chuan)接(jie)在(zai)電(dian)機轉子回路中,不僅可顯著(zhu)提高功率(lv)因數(shu),使電(dian)機定子電(dian)流大幅度降(jiang)低(di),而且電(dian)機溫升明顯降(jiang)低(di),電(dian)機的效率(lv)和過(guo)載能力顯著(zhu)提高。
TP系列(lie)靜(jing)止式(shi)進(jin)(jin)相(xiang)(xiang)器與自(zi)激(ji)(旋轉(zhuan))式(shi)進(jin)(jin)相(xiang)(xiang)機也(ye)不(bu)同。TP系列(lie)靜(jing)止式(shi)進(jin)(jin)相(xiang)(xiang)器采用了(le) 的(de)(de)交-交變(bian)頻(pin)技術和微機、可(ke)控硅控制技術,可(ke)自(zi)動跟蹤電機運行狀態的(de)(de)變(bian)化(hua)并自(zi)動調整相(xiang)(xiang)關參(can)數以達(da)到佳的(de)(de)補償效果,這是自(zi)激(ji)式(shi)進(jin)(jin)相(xiang)(xiang)機無法(fa)做到的(de)(de)。而且,TP系列(lie)靜(jing)止式(shi)進(jin)(jin)相(xiang)(xiang)器從根本(ben)上克服了(le)自(zi)激(ji)式(shi)進(jin)(jin)相(xiang)(xiang)機“整流子”結(jie)構特別怕塵(chen)埃、壽(shou)命短、維修頻(pin)繁(fan)的(de)(de)缺點;具有(you)參(can)數調節容易、主回路(lu)無轉(zhuan)動部件、不(bu)怕灰塵(chen)、可(ke)靠性(xing)高(gao)、使用壽(shou)命長、維護(hu)方便,是理想(xiang)的(de)(de)取代自(zi)激(ji)式(shi)進(jin)(jin)相(xiang)(xiang)機的(de)(de)新(xin)型高(gao)科技產品(pin)。
TP系列靜止(zhi)式進相器可(ke)廣(guang)泛用于水泥、化工、礦山、冶金、鋼鐵、造紙、制藥等行業的大中型高低壓繞線式異步(bu)電機。
二型(xing)號命名
TP系列靜止式進相器型號命名方法(fa)如下:
型號:TP-800,表示(shi)適用于額定轉子電(dian)流不(bu)超過800A的電(dian)機的靜止式(shi)進相器(qi)。
三工作原理
當電(dian)(dian)(dian)(dian)(dian)(dian)機(ji)運行進相(xiang)(xiang)時,進相(xiang)(xiang)器(qi)通過轉子(zi)電(dian)(dian)(dian)(dian)(dian)(dian)流(liu)傳感器(qi)采集到的(de)轉子(zi)電(dian)(dian)(dian)(dian)(dian)(dian)流(liu)信號及(ji)工頻(pin)(pin)電(dian)(dian)(dian)(dian)(dian)(dian)壓提(ti)供(gong)的(de)同(tong)步信號經微(wei)處(chu)理(li)器(qi)CPU進行數據(ju)和相(xiang)(xiang)位(wei)(wei)處(chu)理(li),控制可控硅(gui)的(de)觸(chu)發(fa)信號,調(diao)整由12只晶閘管組成的(de)交—交變頻(pin)(pin)裝置,將降壓后的(de)工頻(pin)(pin)電(dian)(dian)(dian)(dian)(dian)(dian)源變為和轉子(zi)電(dian)(dian)(dian)(dian)(dian)(dian)流(liu)同(tong)頻(pin)(pin)率(lv)(lv),相(xiang)(xiang)位(wei)(wei)滯后90°的(de)附(fu)加電(dian)(dian)(dian)(dian)(dian)(dian)勢加在電(dian)(dian)(dian)(dian)(dian)(dian)機(ji)轉子(zi)回路中。轉子(zi)的(de)電(dian)(dian)(dian)(dian)(dian)(dian)流(liu)和電(dian)(dian)(dian)(dian)(dian)(dian)壓相(xiang)(xiang)位(wei)(wei)因此改變,通過磁場(chang)進而改變電(dian)(dian)(dian)(dian)(dian)(dian)機(ji)定(ding)子(zi)電(dian)(dian)(dian)(dian)(dian)(dian)流(liu)與定(ding)子(zi)電(dian)(dian)(dian)(dian)(dian)(dian)壓的(de)相(xiang)(xiang)位(wei)(wei)角,使電(dian)(dian)(dian)(dian)(dian)(dian)機(ji)的(de)功率(lv)(lv)因數提(ti)高,得(de)到補償。
當電機在某一負載下運(yun)行時,其轉子(zi)電流(liu)(liu)為I2e、定子(zi)電流(liu)(liu)為I1e, 向量圖如(ru)下所示。
從電(dian)機(ji)學(xue)我們知(zhi)道(dao),激(ji)磁電(dian)流(liu)(liu)(liu)Im由(you)關(guan)(guan)系式Im=I1e-I2e,從向量(liang)圖可(ke)得出(chu)(chu)Im。當進(jin)相器的(de)電(dian)勢疊加在轉子(zi)回路后(hou),轉子(zi)電(dian)流(liu)(liu)(liu)的(de)相位變為圖中的(de)I2。由(you)于負(fu)載(zai)不變,激(ji)磁電(dian)流(liu)(liu)(liu)Im不變。此時的(de)定(ding)(ding)子(zi)電(dian)流(liu)(liu)(liu)I1由(you)關(guan)(guan)系式I1=Im+I2從向量(liang)圖可(ke)得出(chu)(chu)I1,如圖所示。從圖中可(ke)以看出(chu)(chu)I1的(de)功(gong)率(lv)因(yin)數角(jiao)和幅值都比I1e小,說明電(dian)機(ji)的(de)功(gong)率(lv)因(yin)數有所提高(gao),定(ding)(ding)子(zi)電(dian)流(liu)(liu)(liu)有所下(xia)降。
進相(xiang)器就是這樣改(gai)變(bian)轉(zhuan)子電(dian)流與轉(zhuan)子電(dian)壓(ya)的相(xiang)位關系,通過磁(ci)場進而改(gai)變(bian)電(dian)機(ji)定子電(dian)流與定子電(dian)壓(ya)的相(xiang)位關系,減小功(gong)率因(yin)(yin)數角,終使電(dian)機(ji)本身的功(gong)率因(yin)(yin)數得以(yi)提高,定子電(dian)流得以(yi)下降,達到對電(dian)機(ji)補償(chang)的目的。
當負載發生改變(bian)(bian)時,微處理器實時檢測電(dian)機(ji)參數的變(bian)(bian)化(hua),并根(gen)據負載的變(bian)(bian)化(hua),動態調整附加(jia)在轉(zhuan)子上(shang)的電(dian)勢幅值(zhi),以使電(dian)機(ji)的功率因數始終保持(chi)在期望值(zhi)上(shang)。
四(si)原理框(kuang)圖
電容式補償的(de)矢量(liang)分析(xi):
電容補償(chang)和進相器補償(chang)的原理圖分別如下:
圖中(zhong),將電(dian)(dian)機進行了等效(xiao)簡化,R1、X1為(wei)電(dian)(dian)機定子等效(xiao)電(dian)(dian)路(lu)的電(dian)(dian)阻(zu)和(he)電(dian)(dian)感(gan),R2、X2為(wei)電(dian)(dian)機轉子等效(xiao)電(dian)(dian)路(lu)的電(dian)(dian)阻(zu)和(he)電(dian)(dian)感(gan),C為(wei)就(jiu)地補償(chang)的電(dian)(dian)容(rong),Uf為(wei)進相器的等效(xiao)電(dian)(dian)路(lu),M為(wei)電(dian)(dian)機的接線點。
從(cong)圖可(ke)以看出,靜(jing)止(zhi)式進相器(qi)和電(dian)(dian)容補(bu)(bu)償(chang)對電(dian)(dian)機的(de)(de)作用(yong)點不(bu)同,電(dian)(dian)容是在電(dian)(dian)機的(de)(de)前端定子側進行(xing)補(bu)(bu)償(chang),其補(bu)(bu)償(chang)范圍是在補(bu)(bu)償(chang)點的(de)(de)前端;靜(jing)止(zhi)式進相器(qi)串聯在電(dian)(dian)機的(de)(de)后端,其補(bu)(bu)償(chang)范圍擴大到了(le)電(dian)(dian)機。
五性能特(te)點(dian)
1、可使電機的(de)功(gong)率(lv)因數提高到0.95以(yi)上,無功(gong)功(gong)率(lv)降低60%以(yi)上。
2、降低定子(zi)電(dian)流10%-20%。
3、降低線損(sun)、銅損(sun)20%-30%。
4、電機溫升降低5%。
5、過載能(neng)力和效率大大提高,電機使用壽命延(yan)長。
6、具有(you)故障自動保護功(gong)能,保障設備長(chang)期安全運行。
7、操作簡(jian)單,安裝調試和(he)維(wei)修(xiu)保(bao)養(yang)均不影(ying)響(xiang)正常生產(chan),半年(nian)內可收回成本(ben)。
六使用條件
1、安裝地點環境溫度≤40℃
2、安(an)裝地點(dian)相對(dui)濕度(du)≤90%
3、 安裝地點無火災、爆炸危險品(pin),無化學腐蝕及(ji)劇烈振動。
4、海拔高(gao)度≤1500M。
5、進相器柜體(ti)上方0.5米內應通風;如(ru)無(wu)地溝(gou),須將進相器柜體(ti)架空0.1米。
注:TP系(xi)列(lie)靜止式進(jin)相器應滿(man)足(zu)上方要(yao)求的(de)使用條件(jian),襄陽拓邦電氣還可提供適用于(yu)高原(yuan)地區(海拔超過1500米(mi))的靜止式進相器(但(dan)用(yong)戶須事(shi)先特(te)別申請)。
七技(ji)術參數(shu)
進 相 器 型 號 |
適 配 電 機 參 數 |
|
額定轉子電流(A) |
額定功率(KW) |
|
TP-400 |
≤400 |
95-800 |
TP-500 |
400-500 |
245-1000 |
TP-600 |
500-600 |
315-1250 |
TP-800 |
600-800 |
630-1600 |
TP-1000 |
800-1000 |
1000-2000 |
TP-1200 |
1000-1200 |
1600-2500 |
TP-1500 |
1200-1500 |
2000以上 |
八(ba)安裝尺寸
1、外型尺寸圖
2、安裝基礎圖(tu)
3、規格尺(chi)寸表(biao)
型號(hao) |
外形尺寸(MM) |
安裝尺寸(MM) |
||||
寬(W) |
深(D) |
高(H) |
寬(E) |
深(F) |
螺(luo)孔(kong) |
|
TP400-600 |
1000 |
760 |
2000 |
780 |
620 |
14 |
TP800-1000 |
1100 |
800 |
2000 |
880 |
650 |
14 |
TP1200-1500 |
1200 |
900 |
2200 |
980 |
750 |
16 |
注:隨著產品不斷更新換代,外形及安裝尺寸會有(you)所變(bian)化,請以具體(ti)的產品為準。
九(jiu)安裝調試(shi)
(一)安裝(zhuang)
1、將(jiang)進相器搬到安裝位置(zhi),注意進相器柜體底部應與地溝相通或架空,首(shou)先是打開柜子的(de)前后門(men),從上(shang)到下,逐(zhu)一地擰(ning)緊螺絲,防止在(zai)運(yun)輸(shu)過程中(zhong)螺絲松動造成(cheng)進相器不(bu)能(neng)正常(chang)工作。
2、準備好(hao)(hao)連接(jie)(jie)【主電(dian)機轉子(zi)至進(jin)相器(qi)接(jie)(jie)觸器(qi)KM13的三(san)根電(dian)纜】、【進(jin)相器(qi)接(jie)(jie)觸器(qi)KM11至主電(dian)機起動柜的三(san)根電(dian)纜】,其線徑應能承載主電(dian)機轉子(zi)額(e)定電(dian)流,比好(hao)(hao)長度并壓好(hao)(hao)接(jie)(jie)頭。
3、進(jin)相器(qi)(qi)(qi)上的(de)(de)電(dian)(dian)(dian)流(liu)表、功(gong)率因數表是(shi)直接從電(dian)(dian)(dian)機(ji)定(ding)子回路(lu)上的(de)(de)電(dian)(dian)(dian)流(liu)互(hu)感(gan)器(qi)(qi)(qi)、電(dian)(dian)(dian)壓(ya)(ya)互(hu)感(gan)器(qi)(qi)(qi)取(qu)信號,要(yao)求(qiu)所用電(dian)(dian)(dian)流(liu)互(hu)感(gan)器(qi)(qi)(qi)副邊(bian)的(de)(de)額(e)定(ding)電(dian)(dian)(dian)流(liu)為5A、電(dian)(dian)(dian)壓(ya)(ya)互(hu)感(gan)器(qi)(qi)(qi)副邊(bian)的(de)(de)額(e)定(ding)電(dian)(dian)(dian)壓(ya)(ya)為100V,若用戶(hu)現用的(de)(de)不滿足該要(yao)求(qiu),則須另行準備符(fu)合上述要(yao)求(qiu)的(de)(de)互(hu)感(gan)器(qi)(qi)(qi)。(注:電(dian)(dian)(dian)壓(ya)(ya)互(hu)感(gan)器(qi)(qi)(qi)僅適用于高壓(ya)(ya)電(dian)(dian)(dian)機(ji),對低(di)壓(ya)(ya)電(dian)(dian)(dian)機(ji),進(jin)相器(qi)(qi)(qi)電(dian)(dian)(dian)壓(ya)(ya)信號直接從定(ding)子回路(lu)取(qu))
4、新電機須(xu)帶上90%以上負(fu)載并正常運轉后才(cai)可調試(shi)進(jin)相器,用(yong)戶在通(tong)知(zhi)我方調試(shi)前,應(ying)調試(shi)好電機、減速(su)機、磨機等其它設備,使其帶上負(fu)載正常運轉,以免延(yan)誤進(jin)相器調試(shi)時(shi)間。
5、各聯(lian)鎖線意(yi)義如下(xia):
(225、227)取(qu)自電(dian)機起動柜星點(dian)短接(jie)接(jie)觸器的(de)輔助常(chang)開點(dian),只有(you)在電(dian)機起動完畢后,進(jin)相器才可以進(jin)相。
(355、357)當(dang)開關柜主(zhu)開關是接觸器(qi)時與(yu)分閘(zha)按(an)鈕并聯;是斷路器(qi)時與(yu)分閘(zha)按(an)鈕串聯, 進(jin)相狀態(tai)下主(zhu)電(dian)機(ji)不(bu)能(neng)停(ting)(ting)機(ji),只有先(xian)退(tui)相才能(neng)停(ting)(ting)主(zhu)機(ji)。
(359、361)串入開(kai)關柜合(he)閘(zha)回路。當KM11吸合(he)時(shi),可以起動電機。
(363、369)從起動柜控制(zhi)電源引單相380V,使KM11與起動柜控制(zhi)回路(lu)同時得電。
(30、32)串(chuan)入(ru)主電(dian)機電(dian)流(liu)計量回路(lu);(40、42)并入(ru)主電(dian)機電(dian)壓計量回路(lu)。(取(qu)A相電(dian)流(liu)則(ze)取(qu)B,C相電(dian)壓,如此類推,電(dian)流(liu)和電(dian)壓不得取(qu)同相)。
(A、B、C、N)接三(san)相(xiang)四線電源,導線橫截面積:TP600以下(xia)用4mm2;TP1000以下(xia)用6mm2;TP1500以下(xia)用10mm2。
6、控(kong)制器(qi)所(suo)有指示燈的含義說(shuo)明如下:
(1)主(zhu)板(中間一塊)的指示燈(deng)(從上往下數)
●L1、L2、L3:電(dian)(dian)機(ji)轉子三相電(dian)(dian)流信號指示(電(dian)(dian)機(ji)運(yun)轉時為循環顯(xian)示狀態(tai);自檢試驗(yan)時為隨機(ji)狀態(tai):或亮、或滅(mie))
●L4:+5V電源指示(保持亮的(de)狀態)
●L5:熱(re)故(gu)障指示(有熱(re)故(gu)障時L5滅)
●L6:缺相及(ji)自動故障保(bao)護指(zhi)示(有缺相故障及(ji)其它故障時L6燈滅)
●L7:+15V電源指示(保持(chi)亮的狀(zhuang)態(tai))
●L8:-15V電源指示(保持(chi)亮(liang)的狀(zhuang)態)
(2)驅動板(兩邊(bian)兩塊)
●分別代表12個可控制硅的觸(chu)發信號(hao)(指示燈均(jun)亮,并有規(gui)律的閃(shan)爍(shuo))
(二)試(shi)驗
1、檢查主電(dian)纜、聯鎖(suo)線、儀表線連接是(shi)否正確(que)。
2、檢查各(ge)器(qi)件螺絲是否緊固。
3、用萬用表測量可控硅(gui)極(ji)間電阻:
●觸發(fa)極(ji)(ji)G與陰極(ji)(ji)K間電阻為幾十歐姆;
●觸發極G與(yu)陽極A間電阻(zu)大于幾(ji)十千歐;
●陰極(ji)K與陽極(ji)A間電阻(zu)大于(yu)幾十千歐;
●陰(yin)極(ji)K與陽極(ji)A用萬(wan)用表200K檔測(ce)量,阻值應從小(xiao)變(bian)化到無限大。
4、合上起動柜電(dian)源(yuan),進相(xiang)器(qi)背面的接觸器(qi)KM11應吸(xi)合,短接225、227;合上進相(xiang)器(qi)電(dian)源(yuan),電(dian)源(yuan)指示燈(deng)亮;控制器(qi)應有電(dian),控制器(qi)上指示燈(deng)亮。
5、控(kong)制器上撥碼(ma)開關打在(zai)ON(上方)位置,中間(jian)主板L1、L2、L3循環亮或滅,L4~L8全亮;兩(liang)邊(bian)兩(liang)塊驅動板指示燈閃爍。
6、按綠色(se)進相按鈕,進相器前面的(de)(de)接觸器KM13吸合,延時后,背面的(de)(de)接觸器KM11斷開,綠色(se)進相指示燈亮,風機運轉,風應(ying)向上吹,主變(bian)壓器副邊電流不超過30A,并且沒有大幅度變(bian)化。
7、按紅色(se)退(tui)相(xiang)(xiang)按鈕(niu),進(jin)(jin)相(xiang)(xiang)器(qi)后面(mian)的接(jie)觸器(qi)KM11吸合(he),延時后,前面(mian)的接(jie)觸器(qi)KM13斷開,綠色(se)進(jin)(jin)相(xiang)(xiang)指示(shi)燈滅,紅色(se)電源指示(shi)燈亮,進(jin)(jin)相(xiang)(xiang)器(qi)即退(tui)出進(jin)(jin)相(xiang)(xiang)狀態(tai)。
8、通電(dian)試驗結束,請務(wu)必斷開225、227。
(三)調試
1、運(yun)行前:控(kong)制器主(zhu)板(ban)上撥碼開(kai)關(guan)應打在(zai)OFF(下方)位置(zhi)。
2、起(qi)動(dong)主電機(ji):打開進(jin)相器前柜門,合(he)上空氣開關,進(jin)相器電源接通,面板上的紅色(se)電源指示燈亮,關閉(bi)柜門,等待主機(ji)起(qi)動(dong)。
3、進(jin)(jin)相(xiang)(xiang):(1)電(dian)機正(zheng)常(chang)運轉(zhuan)后,按綠色進(jin)(jin)相(xiang)(xiang)按鈕(niu),進(jin)(jin)相(xiang)(xiang)器(qi)(qi)前面的接觸(chu)器(qi)(qi)KM13吸合(he),延時后,背面的接觸(chu)器(qi)(qi)KM11斷開,綠色進(jin)(jin)相(xiang)(xiang)指示燈(deng)亮,風機運轉(zhuan),定子電(dian)流(liu)應下降,功率因數應上(shang)升。如果定子電(dian)流(liu)不下降反而上(shang)升,調整同步(bu)變壓器(qi)(qi)上(shang)6V、6V0兩線的位置,再(zai)進(jin)(jin)相(xiang)(xiang)。
(2)測量主變壓器原、副邊電(dian)流,應(ying)無大幅度擺動。
(3)電機定子電流應平穩,無(wu)大幅度擺動(dong)。
(4)六(liu)個電(dian)抗器上端銅排的電(dian)流擺動幅度應一致。
4、退(tui)相(xiang):按紅色(se)退(tui)相(xiang)按鈕,進(jin)相(xiang)器后(hou)面的(de)接觸器KM11吸合,延(yan)時后(hou),前面的(de)接觸器KM13斷開,綠(lv)色(se)進(jin)相(xiang)指示(shi)燈(deng)滅,紅色(se)電源指示(shi)燈(deng)亮(liang),進(jin)相(xiang)器即(ji)退(tui)出(chu)進(jin)相(xiang)狀態。
5、停車:進相器退相后(hou),按下主機停車按鈕,電機即停車。
(四)測量和(he)觀(guan)察
1、測量(liang)可控硅、銅排、交流接觸(chu)器(qi)、電(dian)抗器(qi)、主變壓器(qi)、控制板溫度。
2、測量可控硅(gui)觸(chu)發電壓(ya);主變壓(ya)器一次、二(er)次電流;電抗器輸(shu)入(ru)電流。
3、觀(guan)察(cha)風機運行情況。
4、觀察整體運行情況,有(you)無(wu)異(yi)常響聲或(huo)銅排(pai)有(you)無(wu)大的抖(dou)動現象等。
十使用(yong)維(wei)護
為(wei)確保TP系列靜止式進相器長(chang)期安全(quan)、可(ke)靠地運行(xing),請操作(zuo)人員(yuan)特(te)別注意(yi)以(yi)下事項:
1、嚴禁在進(jin)相(xiang)器(qi)運行期間,切斷進(jin)相(xiang)器(qi)外部電(dian)源。
2、定期(qi)檢(jian)查冷卻風機(ji)運(yun)轉狀況(kuang),冷卻風機(ji)停轉使可(ke)控硅(gui)散熱能(neng)(neng)力(li)下(xia)降,可(ke)能(neng)(neng)燒壞(huai)可(ke)控硅(gui)。
3、定期檢測主變壓器(qi)原、副邊運行(xing)電流。
4、定期(qi)檢測可控(kong)硅、聯接(jie)銅排、交流接(jie)觸器(qi)、電抗器(qi)、主變壓器(qi)、控(kong)制板的溫度。
5、定期(qi)檢(jian)(jian)修主(zhu)回路接觸器(qi)的觸頭。真空(kong)接觸器(qi)定期(qi)檢(jian)(jian)測絕緣(yuan)電(dian)(dian)阻(zu),用5KV或2.5KV搖(yao)表檢(jian)(jian)查,當開關管(guan)絕緣(yuan)電(dian)(dian)阻(zu)小于(yu)100兆歐時,應(ying)加強(qiang)監視,小于(yu)20兆歐時應(ying)立即(ji)更換新管(guan),以延(yan)長接觸器(qi)的使用壽命,保障進相器(qi)及電(dian)(dian)機安(an)全運(yun)行。
6、當進相(xiang)器停用一段時間又(you)重新啟用時, 次(ci)進相(xiang)前應觀察柜內(nei)控制(zhi)單元上各(ge)指示燈是否正常。電機起(qi)動并正常運轉(zhuan)后,各(ge)指示燈顯示如下:
·主板(中間一塊):除(chu)L1,L2,L3周期性循環顯示(shi)外(注意:此指電機(ji)在運轉時的狀(zhuang)態,若(ruo)電機(ji)未轉,該三燈為隨機(ji)狀(zhuang)態),其(qi)它各燈均亮。
·驅(qu)動扳(兩邊(bian)的兩塊):其上面各指示燈均亮(liang)并(bing)有(you)輕微閃爍。
7、當(dang)電機定子電流出現異常大幅擺動時(shi),應立(li)即退相,查出原因并檢修后投入使用。
8、定期打掃柜內衛(wei)生。
十一故(gu)障處理
主電機不能起動(dong) |
端子363、369無380V 電源 |
檢查起動柜(ju)控制(zhi)電源 |
||
|
接觸器KM11不吸合 |
檢查KM11線包及其控制回路 |
||
|
接觸器KM11吸合,但其輔助觸點未閉合 |
檢修其輔助觸點 |
||
|
端子359、361串入合閘回路的線未接通 |
檢查該回路 |
||
不能投入進相 |
空氣開關QF1、QF2、QF3沒合上 |
合上空氣(qi)開關 |
||
|
按鈕STP、ST接觸不良 |
|
||
|
中間繼電器KA11觸點接觸不良 |
|
||
|
主電機起動柜內星點接觸器常開輔助觸點不能閉合(225、227未接通) |
檢(jian)修該接觸(chu)器輔助(zhu)觸(chu)點及連線(xian) |
||
|
KM13不能吸合(he) |
檢查KM13線包及其控制回路 |
||
|
固態繼電器FV損壞或者不導通 |
控制器主控制板L6燈滅 |
檢查主控板7腳對11、12、13腳有無+、-3伏左右電壓,否則更換電流傳感器 |
|
|
|
檢查固態繼電器FV |
FV的3、4腳有直(zhi)流15V電壓,而323、325不(bu)通,須更換該(gai)繼電器 |
|
進相后主電(dian)機停機 |
接入開關柜的KM11、KM13的輔助觸點359、361接觸不好 |
維修該觸點 |
||
|
進(jin)相器投入進(jin)相瞬(shun)間(jian)外部(bu)空氣開關跳閘 |
更換大規格的空氣開關 |
||
進相后無(wu)效果 |
接入主控板的電(dian)流傳感器(qi)信號線錯誤 |
電流傳感器從左到右TA1、TA2、TA3的信號線應分別對應與主控板的13、12、11腳 |
||
|
主(zhu)控板的撥碼開關在自(zi)檢位(wei) |
撥碼開關撥至(zhi)工作位 |
||
|
KM13吸合后KM11未釋(shi)放(時(shi)間繼(ji)電器KT11壞(huai)) |
更換KT11時間繼電器 |
||
|
KM15沒有(you)吸合 |
KM11的輔助觸點301、305接觸不良 |
維修該觸點 |
|
|
|
KM15線圈故障(zhang) |
更換KM15線圈 |
|
|
KM15主觸點接觸不良 |
更換KM15 |
||
|
主變(bian)壓(ya)器原邊開路 |
更換(huan)主變壓器 |
||
進相(xiang)后主電機電流不減反增(zeng) |
同步電(dian)源相序錯誤 |
調換進相器內小變壓器TC上輸出6V、6V0電壓的兩線位置 |
||
|
電機轉速下降(缺相(xiang)(xiang)),自動(dong)退相(xiang)(xiang) |
KM13主觸點(dian)接觸不良 |
維修該觸點 |
|
|
|
電機轉子線松動(dong),進(jin)相時的(de)電流沖擊導致(zhi)缺相 |
檢查電機轉子線 |
|
進相后主電機(ji)電流(liu)擺動(dong)大 |
可控硅擊穿 |
測(ce)量(liang)可控(kong)硅極間電(dian)阻(zu)(詳細方法見調試部(bu)分) |
||
|
觸(chu)發(fa)板損壞 |
測量可控硅控制極與陰極之間應有0.2V以上的直流電壓信號,否則應檢查觸發板 |
||
|
主板的撥碼開關在自檢位 |
撥碼開關撥至工作位 |
||
|
電(dian)機轉子(zi)線松(song)動 |
檢查電機轉子線 |
||
|
當KM13采用節能型線圈時,線圈故障導致KM13進行瞬間來回釋放、吸合,導致主回路接觸不良 |
維修或更換KM13線圈 |
注意:進相器檢修不得在進相(xiang)狀態下進行,發(fa)現問(wen)題應立即(ji)退相(xiang)。
十二控制板檢修
現象(xiang) |
原因 |
對策 |
L1、L2、L3不循環閃爍,L6滅,其它各燈正常 |
轉子缺相 |
檢查接觸器KM2主觸頭是否損壞,若損壞,則維修觸頭或更換接觸器 |
電流(liu)傳感(gan)器器損(sun)壞 |
檢查電流傳感器是否有±2V以上的輸出信號,否則更換傳感器 |
|
主控(kong)板元(yuan)器件損壞 |
依次更換IC210、IC211 |
|
L1、L2、L3不周期性閃爍,其它各燈正常 |
主控(kong)板元(yuan)器件損壞 |
依次更換IC210、IC211、IC205、IC207 |
L6滅,其它各燈正常 |
主控板元器(qi)件損(sun)壞 |
依次更換IC207、IC209 |
L5滅,其它各燈正常 |
散熱器溫度檢(jian)測回(hui)路故(gu)障 |
檢(jian)查溫度開(kai)關及其連線(xian) |
L4、L7、L8全部或部分滅 |
電源故障 |
1、檢查變壓器及控制板是否有±18V電源 2、更換相應的7805、7815、7915 |
F1-L1~L6 或F2-L1~L6部分指示燈亮,主板各燈正常 |
觸發板元器件(jian)損壞 |
1、有一片ULN2004損壞,更換之 2、脈沖變壓器接觸不良,作相應處理 |
F1-L1~L6 或F2-L1~L6指示燈全滅,主板各燈正常 |
觸(chu)發板元器件損(sun)壞 |
1、兩片ULN2004損壞,更換之 2、更換555芯片 |
觸(chu)發板無(wu)電源 |
1、檢查主板7815是否有虛焊 2、檢查觸發板19腳與主板6腳連接是否正常 |
十三(san)注意事項
1、進相器檢修應在(zai)退相狀態(tai)下進行,發(fa)現問題應立即退相。
2、嚴禁隨意帶(dai)電插拔控制板(ban)(ban),檢(jian)修控制板(ban)(ban)時,一定要把空開QF3打下來。
3、更換可控硅(gui)時(shi)應注意(yi)陰、陽極的方向,并壓(ya)緊散熱器(壓(ya)力不要(yao)過(guo)大),裝上(shang)后擰緊所有螺絲,之(zhi)后再(zai)檢測可控硅(gui)各極間(jian)的電(dian)阻情(qing)況(kuang)。若一(yi)只可控硅(gui)擊穿(chuan)在(zai)柜(ju)體上(shang)直接檢測,同一(yi)相的四(si)個(ge)可控硅(gui)均顯(xian)示(shi)擊穿(chuan),此時(shi)應把該組(zu)可控硅(gui)間(jian)的聯(lian)接銅排拆掉再(zai)測 。
十四(si)訂貨須知(zhi)
1、提供電機型號(hao)、額(e)定(ding)功率(lv)、定(ding)子(zi)電壓(ya)、定(ding)子(zi)電流(liu)、轉子(zi)電壓(ya)、轉子(zi)電流(liu)、額(e)定(ding)功率(lv)因數。
2、提(ti)供電機拖(tuo)動負(fu)載的特征及負(fu)載率。
預(yu)知TP系列無環流靜止式進相器的更(geng)多信(xin)息,請撥打襄(xiang)陽拓邦電氣官(guan)網電話(hua): 鄭經理17771133316或咨詢網站客(ke)服!!