TP系列無環流靜止式進相器是(shi)(shi)襄(xiang)陽拓邦電(dian)(dian)(dian)(dian)氣自(zi)選研制(zhi)(zhi)開(kai)發的(de)新(xin)一(yi)代高(gao)(gao)新(xin)技術產品(pin)(pin),是(shi)(shi)一(yi)種(zhong)專為大中(zhong)型繞線(xian)式異步電(dian)(dian)(dian)(dian)動機(ji)設計制(zhi)(zhi)作的(de)就(jiu)地無功(gong)(gong)(gong)功(gong)(gong)(gong)率補償(chang)裝(zhuang)置。它串(chuan)接于電(dian)(dian)(dian)(dian)機(ji)轉(zhuan)子(zi)回路,改(gai)變轉(zhuan)子(zi)電(dian)(dian)(dian)(dian)流與轉(zhuan)子(zi)電(dian)(dian)(dian)(dian)壓(ya)的(de)相(xiang)(xiang)位關系,通過磁場(chang)進而改(gai)變電(dian)(dian)(dian)(dian)機(ji)定(ding)子(zi)電(dian)(dian)(dian)(dian)流與電(dian)(dian)(dian)(dian)壓(ya)的(de)相(xiang)(xiang)位關系,達到提(ti)高(gao)(gao)電(dian)(dian)(dian)(dian)機(ji)自(zi)身功(gong)(gong)(gong)率因(yin)數(shu)、降(jiang)(jiang)低(di)電(dian)(dian)(dian)(dian)機(ji)定(ding)子(zi)電(dian)(dian)(dian)(dian)流和(he)溫升的(de)目的(de)。這種(zhong)方式從根本(ben)(ben)上改(gai)善了電(dian)(dian)(dian)(dian)機(ji)的(de)運行狀(zhuang)況,顯著(zhu)降(jiang)(jiang)低(di)電(dian)(dian)(dian)(dian)機(ji)及電(dian)(dian)(dian)(dian)網的(de)無功(gong)(gong)(gong)損耗(hao),對(dui)節能降(jiang)(jiang)耗(hao)、降(jiang)(jiang)低(di)單位產品(pin)(pin)成本(ben)(ben),提(ti)高(gao)(gao)企業(ye)的(de)經濟效(xiao)益具有重(zhong)要(yao)的(de)意義。
TP系列(lie)無(wu)(wu)環流(liu)靜止式進相器對(dui)無(wu)(wu)功(gong)功(gong)率的(de)(de)(de)(de)(de)補償與(yu)電(dian)(dian)(dian)機定(ding)子(zi)側并聯電(dian)(dian)(dian)容器的(de)(de)(de)(de)(de)補償有著本質的(de)(de)(de)(de)(de)區別。電(dian)(dian)(dian)容補償只是(shi)在(zai)電(dian)(dian)(dian)機之外的(de)(de)(de)(de)(de)電(dian)(dian)(dian)網上對(dui)無(wu)(wu)功(gong)進行補償,減少電(dian)(dian)(dian)網的(de)(de)(de)(de)(de)無(wu)(wu)功(gong)輸入,電(dian)(dian)(dian)網的(de)(de)(de)(de)(de)功(gong)率因數得到提高(gao),但是(shi)電(dian)(dian)(dian)機的(de)(de)(de)(de)(de)無(wu)(wu)功(gong)消耗(hao)并沒有減少,無(wu)(wu)法(fa)改善電(dian)(dian)(dian)機本身的(de)(de)(de)(de)(de)運(yun)行狀況(kuang);而TP系列靜止式進相器是串接在(zai)電(dian)機(ji)轉子回路中,不僅可(ke)顯(xian)著提高(gao)功率因數,使電(dian)機(ji)定子電(dian)流(liu)大幅度降(jiang)低,而且電(dian)機(ji)溫升明顯(xian)降(jiang)低,電(dian)機(ji)的效率和過載能力(li)顯(xian)著提高(gao)。
TP系(xi)列(lie)靜止(zhi)(zhi)(zhi)式進相(xiang)(xiang)(xiang)器與自(zi)(zi)激(ji)(旋轉(zhuan))式進相(xiang)(xiang)(xiang)機(ji)也不同。TP系(xi)列(lie)靜止(zhi)(zhi)(zhi)式進相(xiang)(xiang)(xiang)器采(cai)用(yong)了 的交-交變頻技術(shu)和微機(ji)、可控硅控制技術(shu),可自(zi)(zi)動(dong)(dong)跟蹤(zong)電機(ji)運行狀態的變化(hua)并自(zi)(zi)動(dong)(dong)調整相(xiang)(xiang)(xiang)關參(can)數(shu)以達(da)到(dao)佳的補償效果,這是自(zi)(zi)激(ji)式進相(xiang)(xiang)(xiang)機(ji)無法做到(dao)的。而且(qie),TP系(xi)列(lie)靜止(zhi)(zhi)(zhi)式進相(xiang)(xiang)(xiang)器從根本上克(ke)服(fu)了自(zi)(zi)激(ji)式進相(xiang)(xiang)(xiang)機(ji)“整流子(zi)”結構特別怕塵埃(ai)、壽命短、維(wei)修頻繁的缺點;具有參(can)數(shu)調節容易(yi)、主回路無轉(zhuan)動(dong)(dong)部(bu)件、不怕灰塵、可靠性(xing)高、使用(yong)壽命長、維(wei)護(hu)方(fang)便(bian),是理想(xiang)的取代(dai)自(zi)(zi)激(ji)式進相(xiang)(xiang)(xiang)機(ji)的新型高科技產品(pin)。
TP系列靜(jing)止式(shi)進相器(qi)可(ke)廣泛用于水(shui)泥、化工(gong)、礦山、冶金、鋼鐵、造紙(zhi)、制藥等行業的大中型高低壓繞線式(shi)異步電機(ji)。
二(er)型號命名
TP系列靜止式進相器型號命名方法(fa)如下(xia):
型號:TP-800,表示適用于額(e)定轉子(zi)電(dian)流不超過800A的電(dian)機的靜止式進相器。
三工作原理
當電(dian)機運行進(jin)相(xiang)時,進(jin)相(xiang)器(qi)通過轉(zhuan)子(zi)電(dian)流(liu)傳感器(qi)采集到的(de)(de)(de)(de)轉(zhuan)子(zi)電(dian)流(liu)信號及工(gong)頻電(dian)壓提供的(de)(de)(de)(de)同步信號經微(wei)處理器(qi)CPU進(jin)行數(shu)據和(he)相(xiang)位處理,控(kong)制(zhi)可控(kong)硅的(de)(de)(de)(de)觸發信號,調整由12只晶閘管組成的(de)(de)(de)(de)交(jiao)—交(jiao)變頻裝置,將(jiang)降(jiang)壓后(hou)的(de)(de)(de)(de)工(gong)頻電(dian)源變為(wei)和(he)轉(zhuan)子(zi)電(dian)流(liu)同頻率,相(xiang)位滯后(hou)90°的(de)(de)(de)(de)附加電(dian)勢加在(zai)電(dian)機轉(zhuan)子(zi)回(hui)路中。轉(zhuan)子(zi)的(de)(de)(de)(de)電(dian)流(liu)和(he)電(dian)壓相(xiang)位因(yin)此改變,通過磁(ci)場進(jin)而改變電(dian)機定子(zi)電(dian)流(liu)與(yu)定子(zi)電(dian)壓的(de)(de)(de)(de)相(xiang)位角(jiao),使電(dian)機的(de)(de)(de)(de)功率因(yin)數(shu)提高,得到補償。
當電(dian)機(ji)在某一負載下(xia)運行時,其(qi)轉(zhuan)子(zi)電(dian)流(liu)為(wei)I2e、定子(zi)電(dian)流(liu)為(wei)I1e, 向(xiang)量圖如下(xia)所示。
從電(dian)機學我們知道,激磁電(dian)流Im由關(guan)系式(shi)Im=I1e-I2e,從向量圖(tu)可得出Im。當進相器的(de)電(dian)勢疊加在轉子回路后(hou),轉子電(dian)流的(de)相位變為圖(tu)中的(de)I2。由于負載不變,激磁電(dian)流Im不變。此(ci)時的(de)定子電(dian)流I1由關(guan)系式(shi)I1=Im+I2從向量圖(tu)可得出I1,如圖(tu)所示。從圖(tu)中可以看出I1的(de)功率因數(shu)角和幅(fu)值都比I1e小,說明電(dian)機的(de)功率因數(shu)有(you)所提高,定子電(dian)流有(you)所下降。
進相(xiang)器就是(shi)這樣(yang)改變轉(zhuan)子(zi)電(dian)(dian)流(liu)與轉(zhuan)子(zi)電(dian)(dian)壓的相(xiang)位(wei)(wei)關系(xi),通過磁場(chang)進而(er)改變電(dian)(dian)機定(ding)子(zi)電(dian)(dian)流(liu)與定(ding)子(zi)電(dian)(dian)壓的相(xiang)位(wei)(wei)關系(xi),減小(xiao)功(gong)率(lv)因數角(jiao),終使電(dian)(dian)機本身的功(gong)率(lv)因數得(de)以(yi)提高,定(ding)子(zi)電(dian)(dian)流(liu)得(de)以(yi)下(xia)降,達到對電(dian)(dian)機補償的目的。
當(dang)負載(zai)發生改(gai)變(bian)時,微(wei)處理器實時檢(jian)測電(dian)(dian)機參數的變(bian)化(hua),并根據負載(zai)的變(bian)化(hua),動態調整附(fu)加(jia)在(zai)轉子上的電(dian)(dian)勢幅值,以使電(dian)(dian)機的功率因數始終(zhong)保持在(zai)期望值上。
四(si)原理框圖
電容式補償的矢量分析(xi):
電(dian)容補償和(he)進相器補償的原理(li)圖分別(bie)如(ru)下:
圖(tu)中(zhong),將電(dian)(dian)(dian)機進(jin)行了等效(xiao)(xiao)簡化,R1、X1為(wei)(wei)電(dian)(dian)(dian)機定子(zi)等效(xiao)(xiao)電(dian)(dian)(dian)路的電(dian)(dian)(dian)阻(zu)和電(dian)(dian)(dian)感(gan),R2、X2為(wei)(wei)電(dian)(dian)(dian)機轉(zhuan)子(zi)等效(xiao)(xiao)電(dian)(dian)(dian)路的電(dian)(dian)(dian)阻(zu)和電(dian)(dian)(dian)感(gan),C為(wei)(wei)就(jiu)地補償的電(dian)(dian)(dian)容,Uf為(wei)(wei)進(jin)相器的等效(xiao)(xiao)電(dian)(dian)(dian)路,M為(wei)(wei)電(dian)(dian)(dian)機的接線點。
從圖可(ke)以(yi)看出,靜止(zhi)式進(jin)(jin)相(xiang)器和電容(rong)補(bu)(bu)償對電機的作用點不同,電容(rong)是(shi)在電機的前端(duan)定子側進(jin)(jin)行(xing)補(bu)(bu)償,其補(bu)(bu)償范圍是(shi)在補(bu)(bu)償點的前端(duan);靜止(zhi)式進(jin)(jin)相(xiang)器串(chuan)聯在電機的后端(duan),其補(bu)(bu)償范圍擴大(da)到了(le)電機。
五性能特點
1、可(ke)使(shi)電機的功(gong)(gong)率因數提高到(dao)0.95以上,無(wu)功(gong)(gong)功(gong)(gong)率降低60%以上。
2、降低定子電流10%-20%。
3、降低線損、銅(tong)損20%-30%。
4、電(dian)機(ji)溫升降低5%。
5、過載能力和效率大大提高(gao),電機使用壽命(ming)延長。
6、具有故障(zhang)自動保護功(gong)能,保障(zhang)設(she)備長期安全運行(xing)。
7、操(cao)作簡(jian)單(dan),安裝調試和維修保養均不影響正常生產,半(ban)年(nian)內(nei)可收回成本。
六使用條件
1、安裝(zhuang)地點環境(jing)溫度≤40℃
2、安裝地(di)點相對濕度(du)≤90%
3、 安裝地(di)點無火災、爆炸危險品,無化學腐(fu)蝕及劇烈(lie)振(zhen)動(dong)。
4、海拔高(gao)度≤1500M。
5、進相器柜體(ti)上方0.5米(mi)內應通風(feng);如無地(di)溝(gou),須將(jiang)進相器柜體(ti)架空0.1米(mi)。
注:TP系列靜止(zhi)式進相(xiang)器(qi)應滿足上方要(yao)求的使用條(tiao)件,襄陽拓邦電氣還可提供適(shi)用于高原地區(海拔超過1500米)的靜止式進相器(但(dan)用戶須事(shi)先(xian)特別申請)。
七(qi)技術(shu)參數
進 相 器 型 號 |
適 配 電 機 參 數 |
|
額定轉子電流(A) |
額定功率(KW) |
|
TP-400 |
≤400 |
95-800 |
TP-500 |
400-500 |
245-1000 |
TP-600 |
500-600 |
315-1250 |
TP-800 |
600-800 |
630-1600 |
TP-1000 |
800-1000 |
1000-2000 |
TP-1200 |
1000-1200 |
1600-2500 |
TP-1500 |
1200-1500 |
2000以上 |
八安裝(zhuang)尺寸
1、外型尺寸圖
2、安(an)裝基礎圖(tu)
3、規格尺(chi)寸表
型號(hao) |
外形尺寸(MM) |
安裝尺寸(MM) |
||||
寬(W) |
深(D) |
高(H) |
寬(E) |
深(F) |
螺孔 |
|
TP400-600 |
1000 |
760 |
2000 |
780 |
620 |
14 |
TP800-1000 |
1100 |
800 |
2000 |
880 |
650 |
14 |
TP1200-1500 |
1200 |
900 |
2200 |
980 |
750 |
16 |
注(zhu):隨著產品(pin)不斷更新換代,外形及安裝尺寸會(hui)有所變化,請以具體的產品(pin)為準。
九安裝調試
(一(yi))安裝
1、將進(jin)相(xiang)器搬到安裝位置,注意(yi)進(jin)相(xiang)器柜體底(di)部應與地溝(gou)相(xiang)通(tong)或架空,首先是打開柜子的前后門(men),從上到下(xia),逐一地擰緊(jin)螺(luo)絲(si),防止在運輸過程中(zhong)螺(luo)絲(si)松動造(zao)成(cheng)進(jin)相(xiang)器不能(neng)正常(chang)工作。
2、準備(bei)好(hao)連接【主(zhu)電(dian)機轉子(zi)至(zhi)進(jin)相器(qi)接觸(chu)器(qi)KM13的(de)三根電(dian)纜(lan)】、【進(jin)相器(qi)接觸(chu)器(qi)KM11至(zhi)主(zhu)電(dian)機起動柜的(de)三根電(dian)纜(lan)】,其(qi)線徑(jing)應能承載主(zhu)電(dian)機轉子(zi)額定電(dian)流,比好(hao)長度(du)并壓(ya)好(hao)接頭。
3、進(jin)相器(qi)(qi)上的(de)電(dian)(dian)(dian)流(liu)表(biao)、功率因(yin)數表(biao)是直(zhi)(zhi)接從電(dian)(dian)(dian)機(ji)定子回(hui)路(lu)上的(de)電(dian)(dian)(dian)流(liu)互(hu)(hu)感器(qi)(qi)、電(dian)(dian)(dian)壓(ya)互(hu)(hu)感器(qi)(qi)取(qu)信(xin)號(hao),要(yao)(yao)求所用(yong)電(dian)(dian)(dian)流(liu)互(hu)(hu)感器(qi)(qi)副邊的(de)額定電(dian)(dian)(dian)流(liu)為5A、電(dian)(dian)(dian)壓(ya)互(hu)(hu)感器(qi)(qi)副邊的(de)額定電(dian)(dian)(dian)壓(ya)為100V,若用(yong)戶現用(yong)的(de)不滿(man)足該(gai)要(yao)(yao)求,則須另行準備符合上述要(yao)(yao)求的(de)互(hu)(hu)感器(qi)(qi)。(注:電(dian)(dian)(dian)壓(ya)互(hu)(hu)感器(qi)(qi)僅適用(yong)于高壓(ya)電(dian)(dian)(dian)機(ji),對(dui)低壓(ya)電(dian)(dian)(dian)機(ji),進(jin)相器(qi)(qi)電(dian)(dian)(dian)壓(ya)信(xin)號(hao)直(zhi)(zhi)接從定子回(hui)路(lu)取(qu))
4、新電機(ji)須帶上(shang)90%以(yi)上(shang)負載并正(zheng)常運(yun)轉后才可調(diao)(diao)試進相器(qi)(qi),用戶在通(tong)知我方(fang)調(diao)(diao)試前,應調(diao)(diao)試好電機(ji)、減速機(ji)、磨(mo)機(ji)等其(qi)它設備,使其(qi)帶上(shang)負載正(zheng)常運(yun)轉,以(yi)免(mian)延誤進相器(qi)(qi)調(diao)(diao)試時間。
5、各聯(lian)鎖(suo)線意義如下:
(225、227)取自電機(ji)起動柜星(xing)點短接接觸器的(de)輔助常(chang)開(kai)點,只有在電機(ji)起動完畢(bi)后,進相器才可(ke)以進相。
(355、357)當開關(guan)柜主開關(guan)是接觸器時與分(fen)閘按鈕并聯;是斷路器時與分(fen)閘按鈕串聯, 進相(xiang)狀態(tai)下主電機(ji)不能停機(ji),只(zhi)有先退(tui)相(xiang)才能停主機(ji)。
(359、361)串入(ru)開關柜合閘回路。當KM11吸合時,可以起動電機(ji)。
(363、369)從(cong)起動(dong)柜控(kong)制(zhi)電(dian)源引單相380V,使KM11與起動(dong)柜控(kong)制(zhi)回(hui)路同時得電(dian)。
(30、32)串入(ru)主(zhu)電(dian)(dian)(dian)機(ji)電(dian)(dian)(dian)流計量(liang)回(hui)路(lu);(40、42)并入(ru)主(zhu)電(dian)(dian)(dian)機(ji)電(dian)(dian)(dian)壓(ya)計量(liang)回(hui)路(lu)。(取(qu)A相電(dian)(dian)(dian)流則取(qu)B,C相電(dian)(dian)(dian)壓(ya),如此類推,電(dian)(dian)(dian)流和(he)電(dian)(dian)(dian)壓(ya)不得取(qu)同相)。
(A、B、C、N)接三相(xiang)四(si)線電源,導線橫截面積(ji):TP600以下(xia)用(yong)4mm2;TP1000以下(xia)用(yong)6mm2;TP1500以下(xia)用(yong)10mm2。
6、控(kong)制(zhi)器所有指示燈的含義說明如(ru)下:
(1)主板(中間一塊)的(de)指(zhi)示燈(從上往下數(shu))
●L1、L2、L3:電機(ji)轉(zhuan)子三相電流(liu)信號指示(shi)(電機(ji)運(yun)轉(zhuan)時(shi)為循環顯示(shi)狀態;自檢試驗時(shi)為隨機(ji)狀態:或(huo)亮、或(huo)滅)
●L4:+5V電源指示(保持亮(liang)的狀態)
●L5:熱故(gu)障(zhang)指示(有熱故(gu)障(zhang)時L5滅)
●L6:缺相及自動故(gu)障保護指示(有缺相故(gu)障及其它故(gu)障時L6燈滅)
●L7:+15V電源指示(保持亮的狀態)
●L8:-15V電源指示(保持亮的狀(zhuang)態)
(2)驅動板(兩邊兩塊)
●分(fen)別代表12個可控制硅的觸發信(xin)號(指(zhi)示燈均亮,并(bing)有規律的閃爍)
(二)試驗
1、檢查主電(dian)纜、聯鎖線(xian)、儀表線(xian)連接是(shi)否正(zheng)確。
2、檢查各(ge)器件螺絲是(shi)否緊固。
3、用萬用表測量可控(kong)硅極間電阻:
●觸發(fa)極G與(yu)陰極K間(jian)電(dian)阻為(wei)幾十歐姆;
●觸發極G與陽極A間電阻大(da)于幾(ji)十千歐;
●陰極K與(yu)陽極A間(jian)電阻大于幾十(shi)千歐;
●陰極(ji)K與陽極(ji)A用萬用表(biao)200K檔測量,阻(zu)值(zhi)應從小(xiao)變化(hua)到無限(xian)大。
4、合(he)上(shang)起動柜電源,進(jin)(jin)相(xiang)器背面的(de)接(jie)觸器KM11應吸(xi)合(he),短(duan)接(jie)225、227;合(he)上(shang)進(jin)(jin)相(xiang)器電源,電源指示(shi)燈亮(liang);控制(zhi)器應有電,控制(zhi)器上(shang)指示(shi)燈亮(liang)。
5、控制(zhi)器上(shang)撥(bo)碼開關打在ON(上(shang)方)位置(zhi),中間主板L1、L2、L3循(xun)環亮或滅(mie),L4~L8全亮;兩邊兩塊驅動板指(zhi)示燈閃爍。
6、按(an)綠色進(jin)相按(an)鈕,進(jin)相器前面的接觸器KM13吸合,延(yan)時后,背面的接觸器KM11斷開,綠色進(jin)相指(zhi)示燈亮,風機(ji)運轉,風應向上吹,主變壓器副邊電(dian)流不超過30A,并且沒有大(da)幅度變化。
7、按(an)紅色退(tui)(tui)相(xiang)按(an)鈕,進(jin)(jin)相(xiang)器后(hou)面的接觸器KM11吸(xi)合,延時后(hou),前面的接觸器KM13斷開(kai),綠色進(jin)(jin)相(xiang)指示(shi)燈(deng)滅,紅色電源指示(shi)燈(deng)亮,進(jin)(jin)相(xiang)器即退(tui)(tui)出進(jin)(jin)相(xiang)狀態。
8、通電試驗結束,請務(wu)必斷開225、227。
(三)調試
1、運(yun)行前:控制器主板上(shang)撥(bo)碼(ma)開關應打在OFF(下方(fang))位置。
2、起動主電(dian)機:打(da)開(kai)進(jin)相器(qi)前柜門,合上空氣開(kai)關,進(jin)相器(qi)電(dian)源(yuan)接通,面板上的紅色(se)電(dian)源(yuan)指(zhi)示燈亮(liang),關閉柜門,等待主機起動。
3、進(jin)相:(1)電(dian)(dian)機正常運轉后,按綠色進(jin)相按鈕(niu),進(jin)相器前面的(de)接觸器KM13吸合,延時后,背面的(de)接觸器KM11斷開(kai),綠色進(jin)相指示燈亮(liang),風機運轉,定子(zi)電(dian)(dian)流(liu)應下(xia)降,功(gong)率因數應上(shang)升。如果(guo)定子(zi)電(dian)(dian)流(liu)不(bu)下(xia)降反而上(shang)升,調整同步(bu)變壓器上(shang)6V、6V0兩(liang)線的(de)位置,再進(jin)相。
(2)測量(liang)主變壓器原(yuan)、副邊(bian)電流,應(ying)無(wu)大幅度擺動。
(3)電機定子電流應(ying)平穩,無大幅度(du)擺動。
(4)六個電抗(kang)器上(shang)端銅排(pai)的(de)電流(liu)擺動幅度應一致。
4、退(tui)相(xiang):按(an)紅(hong)色(se)退(tui)相(xiang)按(an)鈕,進相(xiang)器(qi)后面的(de)接觸(chu)器(qi)KM11吸合,延時后,前面的(de)接觸(chu)器(qi)KM13斷開,綠色(se)進相(xiang)指示(shi)燈(deng)滅,紅(hong)色(se)電源指示(shi)燈(deng)亮,進相(xiang)器(qi)即(ji)退(tui)出進相(xiang)狀態。
5、停車:進相(xiang)器(qi)退相(xiang)后,按下主機停車按鈕,電機即停車。
(四)測量(liang)和觀察(cha)
1、測(ce)量可控硅、銅排、交流(liu)接(jie)觸器(qi)、電抗器(qi)、主變壓器(qi)、控制(zhi)板溫(wen)度。
2、測量可控硅(gui)觸發電(dian)(dian)壓;主變壓器(qi)一次、二次電(dian)(dian)流;電(dian)(dian)抗器(qi)輸入(ru)電(dian)(dian)流。
3、觀察風(feng)機(ji)運行情況(kuang)。
4、觀察整體運行情況,有無(wu)異常響(xiang)聲或銅排有無(wu)大的抖動(dong)現象等(deng)。
十使用維護
為確保TP系列靜止式進相器長期(qi)安全、可靠地運行,請操作(zuo)人員特(te)別注(zhu)意以下事項(xiang):
1、嚴禁在進(jin)相(xiang)器運行期間,切斷進(jin)相(xiang)器外部電(dian)源。
2、定期檢查冷(leng)卻風(feng)機運轉狀(zhuang)況(kuang),冷(leng)卻風(feng)機停轉使可控硅(gui)散熱能(neng)(neng)力下(xia)降,可能(neng)(neng)燒壞可控硅(gui)。
3、定期檢(jian)測(ce)主變壓器(qi)原(yuan)、副邊運行電流。
4、定期檢測可控硅、聯接銅(tong)排、交流接觸器(qi)、電抗器(qi)、主變壓器(qi)、控制板的(de)溫度。
5、定期(qi)檢(jian)修主回(hui)路接(jie)觸(chu)器(qi)的觸(chu)頭。真(zhen)空(kong)接(jie)觸(chu)器(qi)定期(qi)檢(jian)測絕緣電阻,用(yong)5KV或2.5KV搖(yao)表檢(jian)查(cha),當開關管(guan)絕緣電阻小于100兆(zhao)(zhao)歐時,應(ying)加強監視,小于20兆(zhao)(zhao)歐時應(ying)立即更換新(xin)管(guan),以延長(chang)接(jie)觸(chu)器(qi)的使用(yong)壽(shou)命,保(bao)障進相(xiang)器(qi)及電機安全運行。
6、當進(jin)相器停用一段時間又重新啟用時, 次進(jin)相前應觀(guan)察(cha)柜內控(kong)制單元上各指示(shi)燈是否正(zheng)(zheng)常。電機起動并正(zheng)(zheng)常運轉后(hou),各指示(shi)燈顯示(shi)如下:
·主板(ban)(中間一塊):除L1,L2,L3周期性循環顯(xian)示外(注(zhu)意:此指(zhi)電機在運轉時的狀(zhuang)態(tai),若電機未轉,該(gai)三燈為(wei)隨(sui)機狀(zhuang)態(tai)),其(qi)它各燈均亮(liang)。
·驅(qu)動扳(兩(liang)邊的兩(liang)塊):其上(shang)面(mian)各(ge)指示燈均(jun)亮并有(you)輕(qing)微閃(shan)爍(shuo)。
7、當電機定子電流出(chu)現異常(chang)大幅(fu)擺動時,應立(li)即(ji)退相,查出(chu)原因并(bing)檢修(xiu)后投入(ru)使用。
8、定期打掃柜內衛(wei)生。
十一故障處(chu)理(li)
主電(dian)機不能起動 |
端子363、369無380V 電源 |
檢查起動柜控制(zhi)電源 |
||
|
接觸器KM11不吸合 |
檢查KM11線包及其控制回路 |
||
|
接觸器KM11吸合,但其輔助觸點未閉合 |
檢修其(qi)輔助觸點 |
||
|
端子359、361串入合閘回路的線未接通 |
檢查該回路 |
||
不能投入進(jin)相 |
空氣開關QF1、QF2、QF3沒合上 |
合(he)上空氣開關(guan) |
||
|
按鈕STP、ST接觸不良 |
|
||
|
中間繼電器KA11觸點接觸不良 |
|
||
|
主電機起動柜內星點接觸器常開輔助觸點不能閉合(225、227未接通) |
檢修該接觸(chu)器輔助觸(chu)點(dian)及連線 |
||
|
KM13不能吸合 |
檢查KM13線包及其控制回路 |
||
|
固態繼電器FV損壞或者不導通 |
控制器主控制板L6燈滅 |
檢查主控板7腳對11、12、13腳有無+、-3伏左右電壓,否則更換電流傳感器 |
|
|
|
檢查固態繼電器FV |
FV的3、4腳(jiao)有(you)直(zhi)流15V電壓,而323、325不通,須更換(huan)該繼電器 |
|
進(jin)相(xiang)后主電機(ji)停機(ji) |
接入開關柜的KM11、KM13的輔助觸點359、361接觸不好 |
維修該(gai)觸(chu)點 |
||
|
進相(xiang)器投(tou)入(ru)進相(xiang)瞬間外部空氣開關跳閘(zha) |
更換(huan)大規格的(de)空氣開關(guan) |
||
進相后無效果 |
接入主控板的電流(liu)傳感器信號線錯誤(wu) |
電流傳感器從左到右TA1、TA2、TA3的信號線應分別對應與主控板的13、12、11腳 |
||
|
主控板的撥碼開關(guan)在自(zi)檢位 |
撥碼開關(guan)撥至工(gong)作位 |
||
|
KM13吸合后KM11未釋放(時間繼電器KT11壞) |
更換KT11時間繼電器 |
||
|
KM15沒有吸合 |
KM11的輔助觸點301、305接觸不良 |
維(wei)修該觸點 |
|
|
|
KM15線(xian)圈故(gu)障 |
更換KM15線圈 |
|
|
KM15主觸(chu)點接觸(chu)不良 |
更換KM15 |
||
|
主變壓器原邊開(kai)路 |
更(geng)換主變壓器 |
||
進相后主電機(ji)電流不減反增 |
同步電源(yuan)相序錯誤(wu) |
調換進相器內小變壓器TC上輸出6V、6V0電壓的兩線位置 |
||
|
電機轉速下降(缺相),自動退(tui)相 |
KM13主(zhu)觸點(dian)接觸不良 |
維修(xiu)該觸(chu)點 |
|
|
|
電(dian)機轉子線松動,進(jin)相(xiang)時(shi)的電(dian)流沖(chong)擊導致缺(que)相(xiang) |
檢查電機轉子線 |
|
進相后主電(dian)機電(dian)流(liu)擺動大 |
可控(kong)硅擊穿(chuan) |
測量可控硅極間電阻(詳細方法見(jian)調試部分) |
||
|
觸(chu)發板損壞 |
測量可控硅控制極與陰極之間應有0.2V以上的直流電壓信號,否則應檢查觸發板 |
||
|
主板的撥碼開關(guan)在自(zi)檢位 |
撥碼(ma)開關撥至(zhi)工作位 |
||
|
電機轉子線松動 |
檢查電(dian)機轉子線 |
||
|
當KM13采用節能型線圈時,線圈故障導致KM13進行瞬間來回釋放、吸合,導致主回路接觸不良 |
維修或更換KM13線圈 |
注意(yi):進相器檢修不得在進相狀態下進行,發(fa)現問題應立(li)即退(tui)相。
十(shi)二控(kong)制(zhi)板檢修
現象(xiang) |
原因 |
對策 |
L1、L2、L3不循環閃爍,L6滅,其它各燈正常 |
轉(zhuan)子缺(que)相 |
檢查接觸器KM2主觸頭是否損壞,若損壞,則維修觸頭或更換接觸器 |
電(dian)流傳感器器損壞 |
檢查電流傳感器是否有±2V以上的輸出信號,否則更換傳感器 |
|
主控(kong)板(ban)元(yuan)器(qi)件損壞 |
依次更換IC210、IC211 |
|
L1、L2、L3不周期性閃爍,其它各燈正常 |
主控板元器件損壞 |
依次更換IC210、IC211、IC205、IC207 |
L6滅,其它各燈正常 |
主控板元器件損(sun)壞 |
依次更換IC207、IC209 |
L5滅,其它各燈正常 |
散熱器溫(wen)度(du)檢測回路故障 |
檢查溫度(du)開(kai)關及(ji)其連線(xian) |
L4、L7、L8全部或部分滅 |
電源故障(zhang) |
1、檢查變壓器及控制板是否有±18V電源 2、更換相應的7805、7815、7915 |
F1-L1~L6 或F2-L1~L6部分指示燈亮,主板各燈正常 |
觸發板元器件損(sun)壞 |
1、有一片ULN2004損壞,更換之 2、脈沖變壓器接觸不良,作相應處理 |
F1-L1~L6 或F2-L1~L6指示燈全滅,主板各燈正常 |
觸發板元器件(jian)損(sun)壞 |
1、兩片ULN2004損壞,更換之 2、更換555芯片 |
觸發板(ban)無電源 |
1、檢查主板7815是否有虛焊 2、檢查觸發板19腳與主板6腳連接是否正常 |
十(shi)三(san)注意(yi)事項
1、進相(xiang)(xiang)器檢修應在(zai)退相(xiang)(xiang)狀態下進行,發現問題應立即退相(xiang)(xiang)。
2、嚴禁隨(sui)意帶電(dian)插拔控制板,檢修(xiu)控制板時,一定要把空開QF3打(da)下來。
3、更換可控(kong)(kong)硅時應注(zhu)意陰、陽(yang)極(ji)的(de)方向,并(bing)壓緊散(san)熱器(壓力不要過大),裝上后擰(ning)緊所有螺(luo)絲,之后再(zai)檢測可控(kong)(kong)硅各極(ji)間(jian)的(de)電阻情況。若一(yi)只(zhi)可控(kong)(kong)硅擊穿(chuan)在柜體上直接(jie)檢測,同一(yi)相的(de)四(si)個可控(kong)(kong)硅均顯示擊穿(chuan),此時應把該組可控(kong)(kong)硅間(jian)的(de)聯(lian)接(jie)銅排拆掉再(zai)測 。
十四訂貨須知
1、提(ti)供電機型號(hao)、額定功率、定子(zi)電壓、定子(zi)電流、轉子(zi)電壓、轉子(zi)電流、額定功率因數。
2、提供電機拖動負(fu)載的特征(zheng)及負(fu)載率(lv)。
預知TP系列無環流靜止式進相器的更多信息,請撥打襄陽拓邦電氣官網電話(hua): 鄭經理17771133316或(huo)咨詢(xun)網站客服!!