TP系列無環流靜止式進相器是(shi)(shi)襄陽拓邦電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)氣自選研(yan)制(zhi)開發(fa)的(de)(de)新(xin)一(yi)代高(gao)新(xin)技術產(chan)品(pin),是(shi)(shi)一(yi)種專為大中型繞線式異步電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)動機(ji)設計制(zhi)作的(de)(de)就地(di)無功(gong)(gong)功(gong)(gong)率(lv)(lv)補償裝置。它串(chuan)接于電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)轉子(zi)(zi)回(hui)路,改(gai)變轉子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)流與轉子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)壓的(de)(de)相位關系,通過磁場進而(er)改(gai)變電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)定子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)流與電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)壓的(de)(de)相位關系,達到提(ti)高(gao)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)自身(shen)功(gong)(gong)率(lv)(lv)因(yin)數(shu)、降(jiang)低(di)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)定子(zi)(zi)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)流和(he)溫(wen)升(sheng)的(de)(de)目的(de)(de)。這種方式從根本(ben)上改(gai)善(shan)了電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)的(de)(de)運行狀況(kuang),顯著降(jiang)低(di)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)機(ji)及(ji)電(dian)(dian)(dian)(dian)(dian)(dian)(dian)(dian)網的(de)(de)無功(gong)(gong)損耗,對節能降(jiang)耗、降(jiang)低(di)單位產(chan)品(pin)成本(ben),提(ti)高(gao)企業的(de)(de)經(jing)濟效益(yi)具有重(zhong)要(yao)的(de)(de)意義。
TP系(xi)列無環流(liu)靜止式進(jin)相(xiang)器對(dui)無功(gong)(gong)功(gong)(gong)率的補(bu)償(chang)與電(dian)機定(ding)子側并(bing)聯電(dian)容器的補(bu)償(chang)有著本質的區別。電(dian)容補(bu)償(chang)只(zhi)是(shi)在電(dian)機之外的電(dian)網上(shang)對(dui)無功(gong)(gong)進(jin)行補(bu)償(chang),減少(shao)電(dian)網的無功(gong)(gong)輸入,電(dian)網的功(gong)(gong)率因數得到提高,但是(shi)電(dian)機的無功(gong)(gong)消耗(hao)并(bing)沒(mei)有減少(shao),無法改善電(dian)機本身的運行狀(zhuang)況;而TP系列靜止式進相器是串接在電(dian)(dian)機(ji)(ji)(ji)轉子回路中,不僅可顯著提(ti)高功率(lv)因數,使電(dian)(dian)機(ji)(ji)(ji)定子電(dian)(dian)流(liu)大幅(fu)度降低,而且電(dian)(dian)機(ji)(ji)(ji)溫升明顯降低,電(dian)(dian)機(ji)(ji)(ji)的效率(lv)和(he)過載能力顯著提(ti)高。
TP系列(lie)(lie)靜(jing)止(zhi)式(shi)(shi)(shi)進相(xiang)(xiang)器(qi)(qi)與(yu)自(zi)激(ji)(ji)(旋轉(zhuan))式(shi)(shi)(shi)進相(xiang)(xiang)機(ji)(ji)(ji)也不同。TP系列(lie)(lie)靜(jing)止(zhi)式(shi)(shi)(shi)進相(xiang)(xiang)器(qi)(qi)采用(yong)了 的(de)(de)交(jiao)-交(jiao)變(bian)頻(pin)技(ji)(ji)術和微機(ji)(ji)(ji)、可控(kong)(kong)硅控(kong)(kong)制技(ji)(ji)術,可自(zi)動(dong)(dong)跟蹤電機(ji)(ji)(ji)運行狀(zhuang)態的(de)(de)變(bian)化(hua)并(bing)自(zi)動(dong)(dong)調整相(xiang)(xiang)關參數以達到佳的(de)(de)補(bu)償效果,這是自(zi)激(ji)(ji)式(shi)(shi)(shi)進相(xiang)(xiang)機(ji)(ji)(ji)無法做到的(de)(de)。而(er)且,TP系列(lie)(lie)靜(jing)止(zhi)式(shi)(shi)(shi)進相(xiang)(xiang)器(qi)(qi)從根本(ben)上克服了自(zi)激(ji)(ji)式(shi)(shi)(shi)進相(xiang)(xiang)機(ji)(ji)(ji)“整流(liu)子”結構特別怕塵(chen)埃(ai)、壽命短、維修(xiu)頻(pin)繁的(de)(de)缺點;具(ju)有參數調節(jie)容易、主回路無轉(zhuan)動(dong)(dong)部件(jian)、不怕灰(hui)塵(chen)、可靠性高、使用(yong)壽命長、維護方便,是理想的(de)(de)取(qu)代(dai)自(zi)激(ji)(ji)式(shi)(shi)(shi)進相(xiang)(xiang)機(ji)(ji)(ji)的(de)(de)新型高科技(ji)(ji)產品。
TP系列靜止(zhi)式(shi)進相器(qi)可廣(guang)泛用于水泥(ni)、化工(gong)、礦(kuang)山(shan)、冶金、鋼鐵、造紙、制藥等(deng)行(xing)業的大(da)中型(xing)高低(di)壓繞(rao)線式(shi)異步電機。
二(er)型(xing)號(hao)命(ming)名
TP系列靜止式進相器型號命名方法(fa)如下:
型(xing)號(hao):TP-800,表示(shi)適用于(yu)額定轉子電(dian)流(liu)不超過800A的(de)電(dian)機的(de)靜止式進相器。
三工作(zuo)原理
當電(dian)機(ji)(ji)運行進(jin)(jin)相(xiang)時(shi),進(jin)(jin)相(xiang)器(qi)通過轉(zhuan)(zhuan)子(zi)(zi)(zi)電(dian)流傳(chuan)感器(qi)采集到(dao)的(de)(de)轉(zhuan)(zhuan)子(zi)(zi)(zi)電(dian)流信(xin)號及工(gong)頻(pin)電(dian)壓(ya)提供的(de)(de)同步信(xin)號經微處理器(qi)CPU進(jin)(jin)行數(shu)據(ju)和相(xiang)位(wei)(wei)處理,控制可(ke)控硅的(de)(de)觸(chu)發(fa)信(xin)號,調整(zheng)由12只晶閘(zha)管(guan)組(zu)成的(de)(de)交(jiao)—交(jiao)變(bian)(bian)頻(pin)裝(zhuang)置,將降壓(ya)后的(de)(de)工(gong)頻(pin)電(dian)源變(bian)(bian)為(wei)和轉(zhuan)(zhuan)子(zi)(zi)(zi)電(dian)流同頻(pin)率(lv),相(xiang)位(wei)(wei)滯后90°的(de)(de)附加(jia)電(dian)勢加(jia)在電(dian)機(ji)(ji)轉(zhuan)(zhuan)子(zi)(zi)(zi)回路中(zhong)。轉(zhuan)(zhuan)子(zi)(zi)(zi)的(de)(de)電(dian)流和電(dian)壓(ya)相(xiang)位(wei)(wei)因(yin)此改變(bian)(bian),通過磁場進(jin)(jin)而改變(bian)(bian)電(dian)機(ji)(ji)定子(zi)(zi)(zi)電(dian)流與(yu)定子(zi)(zi)(zi)電(dian)壓(ya)的(de)(de)相(xiang)位(wei)(wei)角,使電(dian)機(ji)(ji)的(de)(de)功率(lv)因(yin)數(shu)提高(gao),得到(dao)補(bu)償。
當電機在(zai)某一(yi)負(fu)載下運行時,其轉子電流為I2e、定子電流為I1e, 向量圖如下所示。
從(cong)(cong)電機學我(wo)們知(zhi)道,激磁電流(liu)(liu)Im由關系式(shi)Im=I1e-I2e,從(cong)(cong)向(xiang)量(liang)(liang)圖(tu)可得出(chu)Im。當進相(xiang)器(qi)的(de)(de)電勢(shi)疊加在轉子回路(lu)后,轉子電流(liu)(liu)的(de)(de)相(xiang)位變(bian)為(wei)圖(tu)中(zhong)的(de)(de)I2。由于負載不(bu)變(bian),激磁電流(liu)(liu)Im不(bu)變(bian)。此時的(de)(de)定(ding)子電流(liu)(liu)I1由關系式(shi)I1=Im+I2從(cong)(cong)向(xiang)量(liang)(liang)圖(tu)可得出(chu)I1,如圖(tu)所(suo)示(shi)。從(cong)(cong)圖(tu)中(zhong)可以看出(chu)I1的(de)(de)功率因(yin)數角和(he)幅值都比I1e小,說明電機的(de)(de)功率因(yin)數有所(suo)提高,定(ding)子電流(liu)(liu)有所(suo)下降。
進相(xiang)器就是這樣改變轉(zhuan)子(zi)(zi)電(dian)流(liu)與(yu)轉(zhuan)子(zi)(zi)電(dian)壓(ya)(ya)的相(xiang)位(wei)關系(xi),通過磁場進而(er)改變電(dian)機(ji)定(ding)子(zi)(zi)電(dian)流(liu)與(yu)定(ding)子(zi)(zi)電(dian)壓(ya)(ya)的相(xiang)位(wei)關系(xi),減小(xiao)功率(lv)因(yin)數角,終使電(dian)機(ji)本身的功率(lv)因(yin)數得以(yi)提高,定(ding)子(zi)(zi)電(dian)流(liu)得以(yi)下(xia)降,達到(dao)對電(dian)機(ji)補償的目的。
當負(fu)載發生改變時(shi),微處理器實時(shi)檢測電(dian)機參數的(de)變化,并(bing)根據(ju)負(fu)載的(de)變化,動態調整附加(jia)在轉子上的(de)電(dian)勢幅值,以使電(dian)機的(de)功率因數始終保持在期望值上。
四原理(li)框圖
電容式補償(chang)的矢量分析:
電容補償(chang)和(he)進相器補償(chang)的(de)原(yuan)理圖分(fen)別(bie)如下:
圖中,將電(dian)(dian)(dian)機進行了等(deng)(deng)效簡化,R1、X1為電(dian)(dian)(dian)機定子(zi)等(deng)(deng)效電(dian)(dian)(dian)路(lu)的電(dian)(dian)(dian)阻(zu)和(he)電(dian)(dian)(dian)感(gan),R2、X2為電(dian)(dian)(dian)機轉子(zi)等(deng)(deng)效電(dian)(dian)(dian)路(lu)的電(dian)(dian)(dian)阻(zu)和(he)電(dian)(dian)(dian)感(gan),C為就地(di)補償(chang)的電(dian)(dian)(dian)容,Uf為進相(xiang)器的等(deng)(deng)效電(dian)(dian)(dian)路(lu),M為電(dian)(dian)(dian)機的接線點(dian)。
從(cong)圖(tu)可(ke)以看(kan)出(chu),靜(jing)止(zhi)式(shi)進(jin)相(xiang)器和電容補(bu)(bu)償對(dui)電機(ji)(ji)的(de)作用(yong)點不(bu)同,電容是(shi)在(zai)電機(ji)(ji)的(de)前端定子側進(jin)行補(bu)(bu)償,其補(bu)(bu)償范圍是(shi)在(zai)補(bu)(bu)償點的(de)前端;靜(jing)止(zhi)式(shi)進(jin)相(xiang)器串聯(lian)在(zai)電機(ji)(ji)的(de)后端,其補(bu)(bu)償范圍擴大到了電機(ji)(ji)。
五性能特點
1、可使電(dian)機的功率(lv)因數(shu)提高到0.95以(yi)上,無功功率(lv)降低60%以(yi)上。
2、降低定子電(dian)流10%-20%。
3、降低線損(sun)、銅損(sun)20%-30%。
4、電機(ji)溫升降(jiang)低5%。
5、過載(zai)能力和效(xiao)率大大提高,電機使(shi)用壽命(ming)延長。
6、具(ju)有故障自動保護功(gong)能,保障設備長期安全運行。
7、操(cao)作(zuo)簡單,安裝調(diao)試和維修保養均不影響正常生產,半(ban)年內可收回(hui)成本。
六使用(yong)條件(jian)
1、安裝地點環境溫度(du)≤40℃
2、安裝地點相對濕度≤90%
3、 安裝地點無火災、爆炸危險品,無化學腐(fu)蝕及(ji)劇烈振(zhen)動。
4、海拔高度≤1500M。
5、進相器柜(ju)體上(shang)方0.5米內應通風;如無地溝,須將進相器柜(ju)體架空0.1米。
注(zhu):TP系(xi)列(lie)靜止式進(jin)相器應滿足上方(fang)要(yao)求的使用(yong)條件,襄陽拓邦電氣還可提供適用(yong)于高原地區(海拔超過1500米)的靜止式進相器(但(dan)用戶(hu)須事先特(te)別(bie)申(shen)請(qing))。
七(qi)技(ji)術參數
進 相 器 型 號 |
適 配 電 機 參 數 |
|
額定轉子電流(A) |
額定功率(KW) |
|
TP-400 |
≤400 |
95-800 |
TP-500 |
400-500 |
245-1000 |
TP-600 |
500-600 |
315-1250 |
TP-800 |
600-800 |
630-1600 |
TP-1000 |
800-1000 |
1000-2000 |
TP-1200 |
1000-1200 |
1600-2500 |
TP-1500 |
1200-1500 |
2000以上 |
八安裝尺寸
1、外型尺寸圖
2、安裝(zhuang)基礎圖
3、規格尺寸表
型號 |
外形尺寸(MM) |
安裝尺寸(MM) |
||||
寬(W) |
深(D) |
高(H) |
寬(E) |
深(F) |
螺孔 |
|
TP400-600 |
1000 |
760 |
2000 |
780 |
620 |
14 |
TP800-1000 |
1100 |
800 |
2000 |
880 |
650 |
14 |
TP1200-1500 |
1200 |
900 |
2200 |
980 |
750 |
16 |
注:隨著產品(pin)不斷更新換代(dai),外形及安裝尺寸會有所變(bian)化,請以具(ju)體的(de)產品(pin)為準(zhun)。
九安(an)裝調試
(一)安裝
1、將進相器(qi)搬(ban)到安裝位置,注意進相器(qi)柜(ju)(ju)體底部應與地溝(gou)相通或(huo)架空(kong),首先是打(da)開(kai)柜(ju)(ju)子的(de)前后門,從(cong)上(shang)到下,逐一地擰緊螺(luo)絲(si),防止在運輸過程中螺(luo)絲(si)松動造成(cheng)進相器(qi)不能(neng)正(zheng)常工作。
2、準備好(hao)連接【主電(dian)機(ji)(ji)轉子至進相器(qi)接觸(chu)器(qi)KM13的三根電(dian)纜】、【進相器(qi)接觸(chu)器(qi)KM11至主電(dian)機(ji)(ji)起動柜的三根電(dian)纜】,其(qi)線徑應能承載(zai)主電(dian)機(ji)(ji)轉子額定電(dian)流,比好(hao)長(chang)度并壓好(hao)接頭。
3、進(jin)相器上(shang)的電(dian)(dian)流(liu)表(biao)、功率因數表(biao)是(shi)直(zhi)接從(cong)電(dian)(dian)機定子回(hui)(hui)路(lu)上(shang)的電(dian)(dian)流(liu)互(hu)感器、電(dian)(dian)壓互(hu)感器取信號,要(yao)求(qiu)所用電(dian)(dian)流(liu)互(hu)感器副(fu)邊的額(e)定電(dian)(dian)流(liu)為5A、電(dian)(dian)壓互(hu)感器副(fu)邊的額(e)定電(dian)(dian)壓為100V,若用戶現用的不滿足該要(yao)求(qiu),則須另行準備符合上(shang)述要(yao)求(qiu)的互(hu)感器。(注(zhu):電(dian)(dian)壓互(hu)感器僅適用于高壓電(dian)(dian)機,對低壓電(dian)(dian)機,進(jin)相器電(dian)(dian)壓信號直(zhi)接從(cong)定子回(hui)(hui)路(lu)取)
4、新(xin)電(dian)機須帶上90%以上負(fu)載并正(zheng)常運轉后(hou)才可調(diao)(diao)試進相器,用(yong)戶在通知我方(fang)調(diao)(diao)試前,應調(diao)(diao)試好電(dian)機、減速(su)機、磨機等其(qi)它設備,使其(qi)帶上負(fu)載正(zheng)常運轉,以免延誤(wu)進相器調(diao)(diao)試時(shi)間(jian)。
5、各聯(lian)鎖線意義如下:
(225、227)取自電(dian)機起動柜星點短接(jie)接(jie)觸(chu)器(qi)的輔助常開點,只有(you)在電(dian)機起動完畢后,進(jin)相器(qi)才可以進(jin)相。
(355、357)當(dang)開(kai)關柜主開(kai)關是接觸器時與(yu)分閘(zha)(zha)按鈕(niu)并聯;是斷路器時與(yu)分閘(zha)(zha)按鈕(niu)串聯, 進相狀(zhuang)態下主電機不能停機,只(zhi)有先(xian)退(tui)相才(cai)能停主機。
(359、361)串入開(kai)關柜合閘(zha)回路。當(dang)KM11吸合時,可以(yi)起動電(dian)機。
(363、369)從(cong)起動柜控制電源引單相380V,使KM11與(yu)起動柜控制回(hui)路同(tong)時得電。
(30、32)串入(ru)主電(dian)機電(dian)流(liu)計(ji)量回路(lu);(40、42)并(bing)入(ru)主電(dian)機電(dian)壓(ya)(ya)計(ji)量回路(lu)。(取A相電(dian)流(liu)則取B,C相電(dian)壓(ya)(ya),如此類(lei)推,電(dian)流(liu)和電(dian)壓(ya)(ya)不得取同相)。
(A、B、C、N)接三相四線電源(yuan),導線橫截面積:TP600以下(xia)用(yong)4mm2;TP1000以下(xia)用(yong)6mm2;TP1500以下(xia)用(yong)10mm2。
6、控制器所有指(zhi)示燈的含義說(shuo)明(ming)如下:
(1)主板(中(zhong)間一塊)的指示燈(從(cong)上(shang)往下數)
●L1、L2、L3:電機(ji)(ji)轉子三相電流(liu)信(xin)號(hao)指示(shi)(電機(ji)(ji)運轉時(shi)為循環顯(xian)示(shi)狀態;自檢(jian)試驗時(shi)為隨機(ji)(ji)狀態:或亮(liang)、或滅)
●L4:+5V電源(yuan)指示(保持亮的狀態)
●L5:熱故障指示(shi)(有熱故障時L5滅)
●L6:缺(que)相及自動故障(zhang)保護(hu)指示(有缺(que)相故障(zhang)及其它故障(zhang)時L6燈滅)
●L7:+15V電源指示(保持亮(liang)的狀態(tai))
●L8:-15V電(dian)源(yuan)指示(保持(chi)亮的狀(zhuang)態)
(2)驅動板(兩邊兩塊)
●分別(bie)代表(biao)12個可(ke)控(kong)制硅的觸發信號(指示燈均亮,并有規(gui)律的閃(shan)爍)
(二(er))試(shi)驗(yan)
1、檢查主電纜(lan)、聯鎖線(xian)、儀表線(xian)連接是(shi)否正確。
2、檢查各器件螺絲(si)是否(fou)緊固。
3、用萬用表測(ce)量可控(kong)硅極間電(dian)阻(zu):
●觸發極G與陰極K間(jian)電阻為幾(ji)十(shi)歐姆;
●觸發(fa)極(ji)G與(yu)陽(yang)極(ji)A間電阻(zu)大于幾十千(qian)歐;
●陰極K與陽極A間電阻大于幾十千歐;
●陰極K與陽極A用萬用表200K檔測量,阻值應從小變化到(dao)無限(xian)大。
4、合上(shang)起動柜電源(yuan),進相(xiang)器背面(mian)的接觸器KM11應吸合,短接225、227;合上(shang)進相(xiang)器電源(yuan),電源(yuan)指示(shi)(shi)燈(deng)亮;控(kong)制器應有(you)電,控(kong)制器上(shang)指示(shi)(shi)燈(deng)亮。
5、控(kong)制器上撥碼開(kai)關打在ON(上方)位置,中間主板(ban)(ban)L1、L2、L3循(xun)環亮或滅,L4~L8全亮;兩邊兩塊(kuai)驅動板(ban)(ban)指(zhi)示燈閃爍。
6、按綠(lv)色進相(xiang)按鈕,進相(xiang)器(qi)前面(mian)的(de)接(jie)觸(chu)器(qi)KM13吸合,延時(shi)后,背面(mian)的(de)接(jie)觸(chu)器(qi)KM11斷開,綠(lv)色進相(xiang)指示燈亮,風機運轉,風應向(xiang)上吹(chui),主變壓(ya)器(qi)副邊電流不超過30A,并且沒有大幅度變化。
7、按紅(hong)色(se)退相(xiang)按鈕(niu),進相(xiang)器后面的接觸器KM11吸合,延時后,前面的接觸器KM13斷開(kai),綠色(se)進相(xiang)指示燈滅(mie),紅(hong)色(se)電源(yuan)指示燈亮,進相(xiang)器即(ji)退出進相(xiang)狀態。
8、通(tong)電試驗結(jie)束,請(qing)務必斷開225、227。
(三)調試
1、運行前(qian):控制器主板上撥(bo)碼開關應打(da)在OFF(下方)位置。
2、起(qi)動主電(dian)機(ji):打(da)開進(jin)相器前柜門,合上空氣開關,進(jin)相器電(dian)源(yuan)接(jie)通,面板上的紅色電(dian)源(yuan)指(zhi)示燈亮(liang),關閉柜門,等待主機(ji)起(qi)動。
3、進相(xiang)(xiang):(1)電機(ji)正常運轉(zhuan)后,按綠(lv)色進相(xiang)(xiang)按鈕(niu),進相(xiang)(xiang)器(qi)前面(mian)(mian)的接觸器(qi)KM13吸合(he),延時后,背(bei)面(mian)(mian)的接觸器(qi)KM11斷開,綠(lv)色進相(xiang)(xiang)指(zhi)示燈(deng)亮,風(feng)機(ji)運轉(zhuan),定(ding)子電流(liu)應(ying)下降(jiang),功率因數應(ying)上升(sheng)。如(ru)果定(ding)子電流(liu)不下降(jiang)反而上升(sheng),調整(zheng)同步(bu)變壓器(qi)上6V、6V0兩線的位置,再進相(xiang)(xiang)。
(2)測(ce)量主(zhu)變壓(ya)器原、副邊電流,應無大幅(fu)度擺(bai)動(dong)。
(3)電(dian)機定子電(dian)流應平穩,無大幅(fu)度擺動(dong)。
(4)六個電抗器上端銅排的電流擺動(dong)幅度(du)應一致(zhi)。
4、退相(xiang):按(an)紅色(se)退相(xiang)按(an)鈕,進(jin)相(xiang)器(qi)后(hou)面的接觸器(qi)KM11吸合,延時后(hou),前面的接觸器(qi)KM13斷開(kai),綠色(se)進(jin)相(xiang)指示(shi)燈滅,紅色(se)電源指示(shi)燈亮,進(jin)相(xiang)器(qi)即退出進(jin)相(xiang)狀態。
5、停車(che):進相(xiang)(xiang)器退相(xiang)(xiang)后(hou),按下(xia)主機(ji)停車(che)按鈕,電機(ji)即停車(che)。
(四(si))測量和觀察
1、測量可控硅、銅(tong)排、交流接觸器(qi)、電抗器(qi)、主變(bian)壓器(qi)、控制(zhi)板溫度。
2、測量(liang)可控硅觸發電壓;主(zhu)變壓器一次(ci)、二次(ci)電流;電抗(kang)器輸入電流。
3、觀察風機運行情況。
4、觀察整(zheng)體運行情況(kuang),有(you)無異常響聲或銅(tong)排有(you)無大的抖動現象等。
十(shi)使用維護
為確保TP系列靜止式進相器長期安全、可靠地運行,請操作人員(yuan)特別注(zhu)意以下(xia)事項:
1、嚴禁在(zai)進相器運(yun)行(xing)期間,切斷進相器外部電源(yuan)。
2、定期檢查(cha)冷卻風機運轉(zhuan)狀況,冷卻風機停轉(zhuan)使可(ke)控(kong)(kong)硅散熱(re)能力下(xia)降,可(ke)能燒壞可(ke)控(kong)(kong)硅。
3、定期檢(jian)測主變壓器原、副(fu)邊運行電(dian)流。
4、定期檢測可控硅(gui)、聯接(jie)(jie)銅排、交流接(jie)(jie)觸器(qi)、電抗(kang)器(qi)、主變壓器(qi)、控制板(ban)的溫度(du)。
5、定期檢(jian)修主回路接(jie)觸(chu)(chu)器的觸(chu)(chu)頭。真空(kong)接(jie)觸(chu)(chu)器定期檢(jian)測絕(jue)緣電(dian)(dian)阻,用(yong)5KV或2.5KV搖表(biao)檢(jian)查,當開關管絕(jue)緣電(dian)(dian)阻小于100兆歐(ou)時,應(ying)加(jia)強監視,小于20兆歐(ou)時應(ying)立即更換新管,以延長(chang)接(jie)觸(chu)(chu)器的使用(yong)壽命,保障進相(xiang)器及電(dian)(dian)機安(an)全運行。
6、當進相器停用(yong)一段時間又重新啟用(yong)時, 次進相前(qian)應(ying)觀察柜內控制單元上各指示燈是否正常。電機起動并正常運轉后,各指示燈顯示如(ru)下(xia):
·主板(中間一塊(kuai)):除L1,L2,L3周期性(xing)循環顯示外(注意:此(ci)指(zhi)電機在運轉(zhuan)時的狀(zhuang)態(tai),若電機未轉(zhuan),該三燈為隨(sui)機狀(zhuang)態(tai)),其它各燈均(jun)亮。
·驅動扳(兩(liang)邊的兩(liang)塊):其上面各指示燈均亮(liang)并有輕微閃爍。
7、當電機(ji)定子電流出(chu)現異常大(da)幅擺動時,應立(li)即退(tui)相,查(cha)出(chu)原(yuan)因并(bing)檢修后(hou)投入(ru)使用。
8、定(ding)期打掃柜內衛生(sheng)。
十一故障處理
主電機不(bu)能起動 |
端子363、369無380V 電源 |
檢查起(qi)動(dong)柜控(kong)制電源 |
||
|
接觸器KM11不吸合 |
檢查KM11線包及其控制回路 |
||
|
接觸器KM11吸合,但其輔助觸點未閉合 |
檢修(xiu)其輔(fu)助觸(chu)點 |
||
|
端子359、361串入合閘回路的線未接通 |
檢查該回路 |
||
不能投(tou)入進相(xiang) |
空氣開關QF1、QF2、QF3沒合上 |
合上空氣(qi)開關 |
||
|
按鈕STP、ST接觸不良 |
|
||
|
中間繼電器KA11觸點接觸不良 |
|
||
|
主電機起動柜內星點接觸器常開輔助觸點不能閉合(225、227未接通) |
檢修該接觸器(qi)輔(fu)助觸點及連(lian)線(xian) |
||
|
KM13不(bu)能吸合 |
檢查KM13線包及其控制回路 |
||
|
固態繼電器FV損壞或者不導通 |
控制器主控制板L6燈滅 |
檢查主控板7腳對11、12、13腳有無+、-3伏左右電壓,否則更換電流傳感器 |
|
|
|
檢查固態繼電器FV |
FV的3、4腳有(you)直(zhi)流15V電壓,而323、325不通,須更換該繼(ji)電器 |
|
進相(xiang)后主電機(ji)停機(ji) |
接入開關柜的KM11、KM13的輔助觸點359、361接觸不好 |
維修該觸點(dian) |
||
|
進(jin)(jin)相器投入(ru)進(jin)(jin)相瞬間(jian)外部空氣開(kai)關跳(tiao)閘 |
更換大(da)規(gui)格的空氣開關 |
||
進相后無效果(guo) |
接入(ru)主(zhu)控板的電流傳(chuan)感(gan)器信號線錯誤 |
電流傳感器從左到右TA1、TA2、TA3的信號線應分別對應與主控板的13、12、11腳 |
||
|
主(zhu)控板的撥碼開(kai)關在(zai)自檢位 |
撥(bo)碼開關(guan)撥(bo)至工作(zuo)位 |
||
|
KM13吸合(he)后KM11未(wei)釋放(時(shi)間繼電器KT11壞) |
更換KT11時間繼電器 |
||
|
KM15沒有(you)吸合 |
KM11的輔助(zhu)觸點(dian)301、305接觸不良 |
維修該(gai)觸點 |
|
|
|
KM15線(xian)圈故障 |
更換KM15線圈 |
|
|
KM15主(zhu)觸(chu)點(dian)接觸(chu)不良(liang) |
更換KM15 |
||
|
主(zhu)變壓器(qi)原(yuan)邊開路(lu) |
更換主變壓器 |
||
進(jin)相后(hou)主電機電流(liu)不減反增 |
同步電源相序錯誤 |
調換進相器內小變壓器TC上輸出6V、6V0電壓的兩線位置 |
||
|
電機轉速下降(缺相),自動退相 |
KM13主觸(chu)點接觸(chu)不良 |
維(wei)修該(gai)觸點 |
|
|
|
電機(ji)轉子線松動,進相(xiang)時(shi)的(de)電流沖擊導致缺相(xiang) |
檢查(cha)電機(ji)轉子線 |
|
進相后(hou)主電機電流擺動大 |
可控硅擊穿 |
測量可控硅極間電阻(詳細方法(fa)見(jian)調試部分) |
||
|
觸發(fa)板損壞(huai) |
測量可控硅控制極與陰極之間應有0.2V以上的直流電壓信號,否則應檢查觸發板 |
||
|
主板的(de)撥(bo)碼開(kai)關在自檢位(wei) |
撥碼開關撥至工作位 |
||
|
電機轉子線松動 |
檢查電機(ji)轉子線(xian) |
||
|
當KM13采用節能型線圈時,線圈故障導致KM13進行瞬間來回釋放、吸合,導致主回路接觸不良 |
維修或更換KM13線圈 |
注意(yi):進相器檢修不得在進相狀(zhuang)態下進行(xing),發現問題應立即退(tui)相。
十二控制板檢修
現象 |
原因 |
對策 |
L1、L2、L3不循環閃爍,L6滅,其它各燈正常 |
轉子缺相 |
檢查接觸器KM2主觸頭是否損壞,若損壞,則維修觸頭或更換接觸器 |
電(dian)流(liu)傳(chuan)感器器損壞 |
檢查電流傳感器是否有±2V以上的輸出信號,否則更換傳感器 |
|
主控板元器件(jian)損(sun)壞 |
依次更換IC210、IC211 |
|
L1、L2、L3不周期性閃爍,其它各燈正常 |
主控板元器件損壞(huai) |
依次更換IC210、IC211、IC205、IC207 |
L6滅,其它各燈正常 |
主控板元器件損壞 |
依次更換IC207、IC209 |
L5滅,其它各燈正常 |
散熱器溫度檢測回路故障 |
檢查溫(wen)度(du)開關及(ji)其(qi)連線 |
L4、L7、L8全部或部分滅 |
電(dian)源故障 |
1、檢查變壓器及控制板是否有±18V電源 2、更換相應的7805、7815、7915 |
F1-L1~L6 或F2-L1~L6部分指示燈亮,主板各燈正常 |
觸發板元器(qi)件(jian)損(sun)壞 |
1、有一片ULN2004損壞,更換之 2、脈沖變壓器接觸不良,作相應處理 |
F1-L1~L6 或F2-L1~L6指示燈全滅,主板各燈正常 |
觸發板(ban)元(yuan)器件損(sun)壞 |
1、兩片ULN2004損壞,更換之 2、更換555芯片 |
觸發板無電源 |
1、檢查主板7815是否有虛焊 2、檢查觸發板19腳與主板6腳連接是否正常 |
十三注(zhu)意(yi)事(shi)項
1、進相(xiang)器(qi)檢(jian)修應(ying)在退相(xiang)狀態(tai)下進行,發(fa)現(xian)問(wen)題應(ying)立即(ji)退相(xiang)。
2、嚴禁隨意(yi)帶電插拔控(kong)(kong)制板,檢修控(kong)(kong)制板時,一定要把空開QF3打下來(lai)。
3、更換(huan)可控(kong)(kong)硅(gui)(gui)時應注意陰(yin)、陽(yang)極的(de)(de)方向,并(bing)壓緊散熱器(qi)(壓力不要過(guo)大(da)),裝上后擰緊所有(you)螺(luo)絲,之后再檢測可控(kong)(kong)硅(gui)(gui)各極間(jian)的(de)(de)電阻情況(kuang)。若一只可控(kong)(kong)硅(gui)(gui)擊穿(chuan)在柜體上直接檢測,同一相的(de)(de)四個可控(kong)(kong)硅(gui)(gui)均顯示(shi)擊穿(chuan),此時應把該組可控(kong)(kong)硅(gui)(gui)間(jian)的(de)(de)聯接銅排拆掉再測 。
十四(si)訂貨須知
1、提供電(dian)機型號、額(e)定(ding)(ding)(ding)功(gong)率、定(ding)(ding)(ding)子(zi)電(dian)壓(ya)、定(ding)(ding)(ding)子(zi)電(dian)流、轉子(zi)電(dian)壓(ya)、轉子(zi)電(dian)流、額(e)定(ding)(ding)(ding)功(gong)率因數。
2、提(ti)供電機拖動(dong)負(fu)載的(de)特征及負(fu)載率(lv)。
預知TP系列無環流靜止式進相器的更多信息,請(qing)撥(bo)打襄(xiang)陽拓(tuo)邦電氣(qi)官(guan)網電話(hua): 鄭經(jing)理17771133316或咨(zi)詢(xun)網站客服!!