白銀TP系列靜止式進相器

一(yi)(yi)概述TP系列無環(huan)流靜止式進相器(qi)是襄陽拓邦(bang)電氣自選(xuan)研(yan)制開(kai)發的(de)新一(yi)(yi)代高新技術產品,是一(yi)(yi)種專為大(da)中型繞線式異……

相關內容
在線留言
詳情內容
content details

TP系列無環流靜止式進相器是襄(xiang)陽拓邦電(dian)(dian)(dian)氣自選研制開(kai)發(fa)的新一(yi)代高(gao)新技術產品(pin),是一(yi)種(zhong)專為(wei)大(da)中型繞(rao)線(xian)式(shi)異步電(dian)(dian)(dian)動機(ji)設計制作的就地無功功率補償裝置。它(ta)串(chuan)接(jie)于電(dian)(dian)(dian)機(ji)轉子(zi)回路,改變(bian)(bian)轉子(zi)電(dian)(dian)(dian)流(liu)與(yu)轉子(zi)電(dian)(dian)(dian)壓(ya)的相位(wei)關系,通過磁場進而改變(bian)(bian)電(dian)(dian)(dian)機(ji)定子(zi)電(dian)(dian)(dian)流(liu)與(yu)電(dian)(dian)(dian)壓(ya)的相位(wei)關系,達到提高(gao)電(dian)(dian)(dian)機(ji)自身(shen)功率因數、降(jiang)低(di)電(dian)(dian)(dian)機(ji)定子(zi)電(dian)(dian)(dian)流(liu)和溫升的目的。這(zhe)種(zhong)方式(shi)從(cong)根本上改善(shan)了電(dian)(dian)(dian)機(ji)的運行(xing)狀(zhuang)況,顯著(zhu)降(jiang)低(di)電(dian)(dian)(dian)機(ji)及電(dian)(dian)(dian)網的無功損耗,對節能降(jiang)耗、降(jiang)低(di)單(dan)位(wei)產品(pin)成本,提高(gao)企業的經(jing)濟效益具有(you)重要(yao)的意義。


TP系(xi)列(lie)無(wu)(wu)環流靜止(zhi)式進(jin)相(xiang)器對無(wu)(wu)功(gong)功(gong)率的(de)(de)補(bu)償與電(dian)機(ji)定子側并(bing)聯電(dian)容器的(de)(de)補(bu)償有著(zhu)本(ben)質的(de)(de)區別。電(dian)容補(bu)償只(zhi)是(shi)在電(dian)機(ji)之外的(de)(de)電(dian)網上對無(wu)(wu)功(gong)進(jin)行補(bu)償,減少(shao)電(dian)網的(de)(de)無(wu)(wu)功(gong)輸入(ru),電(dian)網的(de)(de)功(gong)率因數得到提(ti)高,但(dan)是(shi)電(dian)機(ji)的(de)(de)無(wu)(wu)功(gong)消耗并(bing)沒有減少(shao),無(wu)(wu)法改善電(dian)機(ji)本(ben)身的(de)(de)運行狀況;而TP系列靜止式進相器是串接在電(dian)(dian)(dian)機(ji)轉子(zi)回路中,不(bu)僅可顯(xian)(xian)著提高功率因數,使電(dian)(dian)(dian)機(ji)定子(zi)電(dian)(dian)(dian)流大幅度(du)降低,而且電(dian)(dian)(dian)機(ji)溫升明(ming)顯(xian)(xian)降低,電(dian)(dian)(dian)機(ji)的效(xiao)率和(he)過載能力顯(xian)(xian)著提高。

TP系列靜止(zhi)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)器(qi)與自激(ji)(旋轉(zhuan))式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)機(ji)(ji)也不同(tong)。TP系列靜止(zhi)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)器(qi)采用(yong)了 的交-交變(bian)頻(pin)技(ji)術和(he)微機(ji)(ji)、可控(kong)硅控(kong)制技(ji)術,可自動跟蹤電機(ji)(ji)運行狀態的變(bian)化并自動調(diao)整(zheng)相(xiang)(xiang)關參(can)數以達到佳的補償效果(guo),這是自激(ji)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)機(ji)(ji)無(wu)法做(zuo)到的。而且,TP系列靜止(zhi)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)器(qi)從根本上(shang)克服(fu)了自激(ji)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)機(ji)(ji)“整(zheng)流(liu)子”結(jie)構特別怕(pa)塵(chen)埃(ai)、壽(shou)(shou)命(ming)短、維修頻(pin)繁的缺(que)點;具有參(can)數調(diao)節容易、主回路無(wu)轉(zhuan)動部件、不怕(pa)灰塵(chen)、可靠(kao)性(xing)高、使(shi)用(yong)壽(shou)(shou)命(ming)長、維護方便,是理想的取代(dai)自激(ji)式(shi)(shi)(shi)進(jin)(jin)(jin)相(xiang)(xiang)機(ji)(ji)的新(xin)型高科技(ji)產品(pin)。

TP系列靜止式進相(xiang)器(qi)可廣泛用于水泥、化工(gong)、礦山、冶金(jin)、鋼鐵(tie)、造紙、制藥等行業(ye)的大中型高低壓(ya)繞(rao)線(xian)式異步電機。


二型號命(ming)名

TP系列靜止式進相器型號命名方法如下:





型號(hao):TP-800,表示適用于額定轉子電流不超過800A的電機的靜止式進相器(qi)。


三工作原(yuan)理(li)

當電(dian)(dian)機(ji)運行(xing)進相(xiang)時,進相(xiang)器通(tong)過(guo)轉(zhuan)子(zi)電(dian)(dian)流傳感器采集(ji)到的(de)(de)(de)轉(zhuan)子(zi)電(dian)(dian)流信號(hao)及工頻電(dian)(dian)壓提供的(de)(de)(de)同步信號(hao)經微處(chu)理(li)器CPU進行(xing)數(shu)據和(he)相(xiang)位處(chu)理(li),控(kong)(kong)制可控(kong)(kong)硅的(de)(de)(de)觸發信號(hao),調(diao)整由12只晶閘管組成的(de)(de)(de)交(jiao)—交(jiao)變頻裝(zhuang)置,將降壓后的(de)(de)(de)工頻電(dian)(dian)源(yuan)變為和(he)轉(zhuan)子(zi)電(dian)(dian)流同頻率,相(xiang)位滯后90°的(de)(de)(de)附(fu)加電(dian)(dian)勢加在電(dian)(dian)機(ji)轉(zhuan)子(zi)回路中。轉(zhuan)子(zi)的(de)(de)(de)電(dian)(dian)流和(he)電(dian)(dian)壓相(xiang)位因(yin)(yin)此改變,通(tong)過(guo)磁場進而改變電(dian)(dian)機(ji)定子(zi)電(dian)(dian)流與定子(zi)電(dian)(dian)壓的(de)(de)(de)相(xiang)位角,使電(dian)(dian)機(ji)的(de)(de)(de)功率因(yin)(yin)數(shu)提高,得到補償(chang)。

當電機在某一負載(zai)下運行時,其轉子(zi)電流為I2e、定子(zi)電流為I1e, 向量圖如下所示。







從(cong)電(dian)機學我們知道,激(ji)磁電(dian)流(liu)Im由關(guan)系式(shi)Im=I1e-I2e,從(cong)向(xiang)量(liang)圖可得出(chu)Im。當進相器的(de)電(dian)勢疊加在(zai)轉子(zi)回路(lu)后,轉子(zi)電(dian)流(liu)的(de)相位變(bian)為(wei)圖中(zhong)的(de)I2。由于負載不變(bian),激(ji)磁電(dian)流(liu)Im不變(bian)。此(ci)時的(de)定(ding)子(zi)電(dian)流(liu)I1由關(guan)系式(shi)I1=Im+I2從(cong)向(xiang)量(liang)圖可得出(chu)I1,如圖所(suo)示。從(cong)圖中(zhong)可以看出(chu)I1的(de)功(gong)率因(yin)數角和幅值(zhi)都比I1e小,說明電(dian)機的(de)功(gong)率因(yin)數有所(suo)提高,定(ding)子(zi)電(dian)流(liu)有所(suo)下(xia)降(jiang)。

進(jin)相器就是這樣改變轉(zhuan)子(zi)電(dian)流(liu)與(yu)(yu)轉(zhuan)子(zi)電(dian)壓的(de)(de)(de)(de)相位(wei)關(guan)系,通(tong)過磁場進(jin)而改變電(dian)機定(ding)(ding)子(zi)電(dian)流(liu)與(yu)(yu)定(ding)(ding)子(zi)電(dian)壓的(de)(de)(de)(de)相位(wei)關(guan)系,減小功(gong)率(lv)因數角,終(zhong)使(shi)電(dian)機本身(shen)的(de)(de)(de)(de)功(gong)率(lv)因數得以提高(gao),定(ding)(ding)子(zi)電(dian)流(liu)得以下降,達到對電(dian)機補償(chang)的(de)(de)(de)(de)目(mu)的(de)(de)(de)(de)。

當負(fu)載發生改變時(shi),微處理器實(shi)時(shi)檢測電(dian)機參數的(de)變化,并(bing)根據負(fu)載的(de)變化,動態調整(zheng)附加在(zai)轉(zhuan)子上(shang)的(de)電(dian)勢幅值,以使電(dian)機的(de)功(gong)率因數始終(zhong)保(bao)持在(zai)期望值上(shang)。

四原理框圖(tu)






電容式補(bu)償(chang)的矢量分析:








電容(rong)補(bu)償和進相器補(bu)償的原理圖分(fen)別如下(xia):






圖中(zhong),將電(dian)(dian)機(ji)(ji)進(jin)行(xing)了等(deng)效(xiao)簡化,R1、X1為(wei)電(dian)(dian)機(ji)(ji)定子等(deng)效(xiao)電(dian)(dian)路(lu)的(de)(de)電(dian)(dian)阻(zu)和電(dian)(dian)感,R2、X2為(wei)電(dian)(dian)機(ji)(ji)轉子等(deng)效(xiao)電(dian)(dian)路(lu)的(de)(de)電(dian)(dian)阻(zu)和電(dian)(dian)感,C為(wei)就地補(bu)償的(de)(de)電(dian)(dian)容(rong),Uf為(wei)進(jin)相器的(de)(de)等(deng)效(xiao)電(dian)(dian)路(lu),M為(wei)電(dian)(dian)機(ji)(ji)的(de)(de)接(jie)線點。

從圖可以看(kan)出,靜止(zhi)式進相器(qi)和電(dian)容補(bu)償對電(dian)機的作(zuo)用點不(bu)同,電(dian)容是在電(dian)機的前端定子側進行補(bu)償,其補(bu)償范圍是在補(bu)償點的前端;靜止(zhi)式進相器(qi)串聯在電(dian)機的后端,其補(bu)償范圍擴(kuo)大到了電(dian)機。

五性能特點

1、可使電(dian)機(ji)的功(gong)(gong)率因(yin)數提(ti)高到0.95以上,無功(gong)(gong)功(gong)(gong)率降(jiang)低60%以上。

2、降低定子電流10%-20%。

3、降(jiang)低線損、銅損20%-30%。

4、電(dian)機溫(wen)升降(jiang)低5%。

5、過載能力和效率大(da)大(da)提高,電機使(shi)用(yong)壽命延長(chang)。

6、具有故障自動保(bao)護功能,保(bao)障設(she)備長期(qi)安(an)全運行(xing)。

7、操作簡單,安裝調試和(he)維修保養(yang)均不影響正常(chang)生產,半年內可(ke)收回成本。

六(liu)使用條件

1、安裝地點環境溫度≤40℃

2、安裝(zhuang)地點(dian)相對濕度≤90%

3、 安裝地點無火災、爆炸危險品,無化學腐蝕及劇(ju)烈振(zhen)動。

4、海拔高(gao)度≤1500M。

5、進相器(qi)(qi)柜(ju)體上方0.5米(mi)內應通風;如(ru)無(wu)地(di)溝,須將進相器(qi)(qi)柜(ju)體架空0.1米(mi)。

注:TP系列靜止(zhi)式(shi)進相器應滿足上(shang)方要求的使用條件,襄陽拓邦電氣還可提供適用于高原地區(海(hai)拔(ba)超(chao)過1500米(mi))的靜止式進相器(但用戶須事先特(te)別申請)。

七技術參數


相 器 型 號

配 電 機 參 數

額定轉子電流(A

額定功率(KW

TP-400

400

95-800

TP-500

400-500

245-1000

TP-600

500-600

315-1250

TP-800

600-800

630-1600

TP-1000

800-1000

1000-2000

TP-1200

1000-1200

1600-2500

TP-1500

1200-1500

2000以上




八安裝尺寸

1、外型尺寸圖






2、安裝基(ji)礎圖







3、規格尺寸表



型號(hao)

外形尺寸(MM)

安裝尺寸(MM)

(W)

(D)

(H)

(E)

(F)

螺孔

TP400-600

1000

760

2000

780

620

14

TP800-1000

1100

800

2000

880

650

14

TP1200-1500

1200

900

2200

980

750

16



注:隨著產(chan)品不斷更(geng)新換代,外形及安裝(zhuang)尺寸會(hui)有所(suo)變化,請以具體(ti)的產(chan)品為準。

九安(an)裝(zhuang)調試

(一)安裝

1、將進(jin)(jin)相(xiang)(xiang)器搬(ban)到安裝位置,注(zhu)意進(jin)(jin)相(xiang)(xiang)器柜(ju)體底部應與地溝相(xiang)(xiang)通或(huo)架空(kong),首(shou)先(xian)是打開(kai)柜(ju)子的前(qian)后門,從上到下,逐一地擰緊螺(luo)絲(si),防止在(zai)運(yun)輸過程中螺(luo)絲(si)松動(dong)造成進(jin)(jin)相(xiang)(xiang)器不能正(zheng)常工作。

2、準備好連接(jie)(jie)【主(zhu)電機轉(zhuan)子(zi)至進相(xiang)器(qi)接(jie)(jie)觸(chu)器(qi)KM13的三根電纜(lan)】、【進相(xiang)器(qi)接(jie)(jie)觸(chu)器(qi)KM11至主(zhu)電機起(qi)動(dong)柜(ju)的三根電纜(lan)】,其線徑應能承載(zai)主(zhu)電機轉(zhuan)子(zi)額定(ding)電流,比好長度(du)并壓好接(jie)(jie)頭。

3、進(jin)相器(qi)(qi)上的(de)(de)電(dian)(dian)流表、功(gong)率因數表是直(zhi)接從電(dian)(dian)機(ji)定(ding)子回路上的(de)(de)電(dian)(dian)流互感(gan)器(qi)(qi)、電(dian)(dian)壓(ya)互感(gan)器(qi)(qi)取信號,要求所用(yong)(yong)電(dian)(dian)流互感(gan)器(qi)(qi)副邊的(de)(de)額定(ding)電(dian)(dian)流為(wei)5A、電(dian)(dian)壓(ya)互感(gan)器(qi)(qi)副邊的(de)(de)額定(ding)電(dian)(dian)壓(ya)為(wei)100V,若用(yong)(yong)戶現用(yong)(yong)的(de)(de)不(bu)滿(man)足該要求,則須(xu)另行(xing)準備符合上述要求的(de)(de)互感(gan)器(qi)(qi)。(注(zhu):電(dian)(dian)壓(ya)互感(gan)器(qi)(qi)僅(jin)適用(yong)(yong)于高壓(ya)電(dian)(dian)機(ji),對(dui)低壓(ya)電(dian)(dian)機(ji),進(jin)相器(qi)(qi)電(dian)(dian)壓(ya)信號直(zhi)接從定(ding)子回路取)

4、新電(dian)機(ji)(ji)須帶(dai)上90%以上負載并正常運轉(zhuan)(zhuan)后才可(ke)調(diao)(diao)試進相器(qi),用戶在通知(zhi)我方(fang)調(diao)(diao)試前,應調(diao)(diao)試好電(dian)機(ji)(ji)、減速機(ji)(ji)、磨(mo)機(ji)(ji)等其它設備,使(shi)其帶(dai)上負載正常運轉(zhuan)(zhuan),以免(mian)延誤進相器(qi)調(diao)(diao)試時間(jian)。

5、各聯鎖線意(yi)義如下:

(225、227)取自(zi)電(dian)機起動柜星點短接(jie)接(jie)觸器的輔助常開點,只有(you)在電(dian)機起動完畢(bi)后(hou),進相(xiang)器才可以進相(xiang)。

(355、357)當(dang)開(kai)(kai)關柜主(zhu)開(kai)(kai)關是接觸器時與(yu)分(fen)閘按鈕并聯(lian);是斷路(lu)器時與(yu)分(fen)閘按鈕串(chuan)聯(lian), 進相(xiang)狀態(tai)下主(zhu)電機(ji)不(bu)能停(ting)(ting)機(ji),只有先退相(xiang)才能停(ting)(ting)主(zhu)機(ji)。

(359、361)串(chuan)入開關柜合閘回路。當KM11吸合時,可以(yi)起(qi)動電(dian)機。

(363、369)從起動柜控(kong)制電(dian)源引單相380V,使(shi)KM11與起動柜控(kong)制回路同(tong)時得電(dian)。

(30、32)串入主電(dian)(dian)機電(dian)(dian)流計量(liang)回(hui)路(lu)(lu);(40、42)并入主電(dian)(dian)機電(dian)(dian)壓(ya)(ya)計量(liang)回(hui)路(lu)(lu)。(取A相電(dian)(dian)流則取B,C相電(dian)(dian)壓(ya)(ya),如此類推(tui),電(dian)(dian)流和電(dian)(dian)壓(ya)(ya)不得取同相)。

(A、B、C、N)接三相四線電源,導線橫(heng)截面積:TP600以下用4mm2;TP1000以下用6mm2;TP1500以下用10mm2。

6、控制器(qi)所(suo)有指示燈的含義(yi)說明如(ru)下:

(1)主板(中間一塊(kuai))的指示燈(從上往(wang)下數(shu))

●L1、L2、L3:電(dian)機(ji)轉子三相電(dian)流信號(hao)指(zhi)示(shi)(電(dian)機(ji)運轉時(shi)為循環(huan)顯示(shi)狀態;自檢試驗時(shi)為隨(sui)機(ji)狀態:或亮、或滅)

●L4:+5V電源指(zhi)示(保持亮的狀態)

●L5:熱(re)故(gu)障指(zhi)示(有熱(re)故(gu)障時L5滅)

●L6:缺相(xiang)及自動故(gu)(gu)障(zhang)保護指示(有缺相(xiang)故(gu)(gu)障(zhang)及其(qi)它(ta)故(gu)(gu)障(zhang)時(shi)L6燈滅(mie))

●L7:+15V電源指(zhi)示(保持亮的狀態)

●L8:-15V電源指示(shi)(保持亮(liang)的狀態)

(2)驅動板(兩邊兩塊)

●分別代表12個可控制(zhi)硅的觸發信號(指示(shi)燈均亮(liang),并有規(gui)律的閃爍)

(二)試驗

1、檢查主(zhu)電(dian)纜、聯鎖線、儀表線連(lian)接是否正確。

2、檢(jian)查各器件(jian)螺絲是否緊固。

3、用萬用表測量可控(kong)硅極間電阻:

●觸發極G與陰極K間電阻為幾十歐姆;

●觸發極G與陽極A間電阻(zu)大于幾十千歐(ou);

●陰極K與陽(yang)極A間(jian)電阻大(da)于幾(ji)十千歐;

●陰(yin)極(ji)K與陽極(ji)A用萬用表(biao)200K檔測(ce)量,阻值應從小(xiao)變(bian)化到無限大。

4、合上起動(dong)柜電(dian)源,進相器背面的接(jie)觸器KM11應吸合,短接(jie)225、227;合上進相器電(dian)源,電(dian)源指(zhi)示燈亮;控制(zhi)器應有(you)電(dian),控制(zhi)器上指(zhi)示燈亮。

5、控制(zhi)器(qi)上撥碼(ma)開關打在(zai)ON(上方)位(wei)置,中間主板(ban)L1、L2、L3循(xun)環(huan)亮或滅,L4~L8全亮;兩邊(bian)兩塊驅動板(ban)指(zhi)示燈閃爍。

6、按(an)(an)綠(lv)色進(jin)(jin)相按(an)(an)鈕,進(jin)(jin)相器前面的接觸器KM13吸合,延(yan)時后(hou),背面的接觸器KM11斷(duan)開,綠(lv)色進(jin)(jin)相指(zhi)示燈亮,風(feng)機運轉(zhuan),風(feng)應向(xiang)上吹(chui),主變壓器副邊電流不超過(guo)30A,并且(qie)沒有大幅度變化。

7、按紅(hong)色(se)(se)退相(xiang)(xiang)(xiang)按鈕,進(jin)相(xiang)(xiang)(xiang)器后面的接觸器KM11吸合,延(yan)時后,前面的接觸器KM13斷開,綠色(se)(se)進(jin)相(xiang)(xiang)(xiang)指示燈(deng)(deng)滅,紅(hong)色(se)(se)電源指示燈(deng)(deng)亮,進(jin)相(xiang)(xiang)(xiang)器即退出進(jin)相(xiang)(xiang)(xiang)狀態。

8、通電試驗結束,請(qing)務必斷開225、227。

(三)調試

1、運(yun)行前:控制器主板上撥碼開關應打在OFF(下方)位置。

2、起(qi)動主電機(ji):打開進相(xiang)器前(qian)柜門,合上空氣開關,進相(xiang)器電源接通(tong),面板上的紅(hong)色電源指示燈(deng)亮,關閉柜門,等待主機(ji)起(qi)動。

3、進相(xiang)(xiang):(1)電(dian)機正常運轉(zhuan)后(hou),按(an)綠(lv)色(se)進相(xiang)(xiang)按(an)鈕,進相(xiang)(xiang)器(qi)前(qian)面(mian)(mian)的接觸器(qi)KM13吸合(he),延時后(hou),背面(mian)(mian)的接觸器(qi)KM11斷(duan)開(kai),綠(lv)色(se)進相(xiang)(xiang)指示(shi)燈亮,風(feng)機運轉(zhuan),定子(zi)電(dian)流應下降,功率因數(shu)應上升。如果定子(zi)電(dian)流不下降反而上升,調整同步變壓器(qi)上6V、6V0兩線的位(wei)置,再(zai)進相(xiang)(xiang)。

(2)測量主變(bian)壓(ya)器原、副邊(bian)電流,應無(wu)大幅度擺動。

(3)電機(ji)定子電流應平穩(wen),無大幅度擺動。

(4)六個電(dian)抗器上(shang)端銅排的電(dian)流(liu)擺動(dong)幅度應一致。

4、退(tui)相(xiang):按(an)紅色退(tui)相(xiang)按(an)鈕,進相(xiang)器(qi)后(hou)(hou)面(mian)的接觸器(qi)KM11吸合(he),延時后(hou)(hou),前面(mian)的接觸器(qi)KM13斷開,綠色進相(xiang)指(zhi)示(shi)燈滅,紅色電源(yuan)指(zhi)示(shi)燈亮(liang),進相(xiang)器(qi)即退(tui)出進相(xiang)狀態。

5、停(ting)車(che)(che):進相器退(tui)相后(hou),按下主(zhu)機停(ting)車(che)(che)按鈕,電機即停(ting)車(che)(che)。

(四)測量(liang)和觀察

1、測量可控硅、銅排、交流(liu)接觸器、電抗器、主變壓器、控制板溫(wen)度。

2、測(ce)量可控硅觸發電(dian)壓;主變壓器一次、二次電(dian)流;電(dian)抗(kang)器輸入電(dian)流。

3、觀察風機運行情況。

4、觀察整(zheng)體運行(xing)情況,有無(wu)異常響聲或(huo)銅排有無(wu)大的(de)抖動(dong)現象等。

十使用(yong)維護

為確保TP系列靜止式進相器長(chang)期安全(quan)、可靠地運行(xing),請操作人(ren)員特別(bie)注意以下事項:

1、嚴禁在進(jin)相器運(yun)行(xing)期間(jian),切斷進(jin)相器外(wai)部電源(yuan)。

2、定期檢查冷卻(que)風(feng)機(ji)運轉狀況(kuang),冷卻(que)風(feng)機(ji)停轉使可(ke)(ke)(ke)控硅散熱能(neng)力下降,可(ke)(ke)(ke)能(neng)燒壞可(ke)(ke)(ke)控硅。

3、定期檢測主變壓器(qi)原、副邊運行電流。

4、定期檢測可控硅、聯接銅排(pai)、交流(liu)接觸(chu)器、電(dian)抗器、主變壓器、控制板的溫度。

5、定(ding)期檢修主回路接觸器的(de)觸頭(tou)。真空接觸器定(ding)期檢測絕緣電阻,用(yong)5KV或2.5KV搖表檢查,當開(kai)關管絕緣電阻小于(yu)(yu)100兆(zhao)歐時(shi),應加(jia)強監視,小于(yu)(yu)20兆(zhao)歐時(shi)應立(li)即更換新(xin)管,以延長接觸器的(de)使用(yong)壽命,保障進相器及電機(ji)安(an)全(quan)運行。

6、當進(jin)相器停(ting)用(yong)一段時間又重新(xin)啟用(yong)時, 次進(jin)相前(qian)應觀察柜內控制單(dan)元上各指示燈是否(fou)正常。電機起動并正常運轉(zhuan)后,各指示燈顯示如下(xia):

·主板(中間一塊):除L1,L2,L3周期性循(xun)環顯示(shi)外(注(zhu)意:此(ci)指電(dian)機在運(yun)轉時的狀(zhuang)態(tai),若電(dian)機未轉,該三(san)燈為(wei)隨(sui)機狀(zhuang)態(tai)),其(qi)它各燈均亮(liang)。

·驅動扳(兩邊的兩塊):其上面各指示燈(deng)均(jun)亮(liang)并(bing)有(you)輕微閃爍。

7、當電(dian)機定子(zi)電(dian)流出(chu)(chu)現異常大幅(fu)擺動時,應立即(ji)退相,查出(chu)(chu)原因(yin)并檢(jian)修后投入使用。

8、定期打(da)掃柜內衛生。

十一(yi)故障處理(li)



主電機(ji)不能起動(dong)

端子363、369無380V 電源

檢查起動柜控制電源(yuan)

 

接觸器KM11不吸合

檢查KM11線包及其控制回路

 

接觸器KM11吸合,但其輔助觸點未閉合

檢(jian)修其(qi)輔助觸點

 

端子359、361串入合閘回路的線未接通

檢(jian)查該回(hui)路

不能(neng)投入進(jin)相

空氣開關QF1、QF2、QF3沒合上

合上空氣開關

 

按鈕STP、ST接觸不良

 

 

中間繼電器KA11觸點接觸不良

 

 

主電機起動柜內星點接觸器常開輔助觸點不能閉合(225、227未接通)

檢修該接觸(chu)器輔助觸(chu)點及(ji)連線

 

KM13不能吸合

檢查KM13線包及其控制回路

 

固態繼電器FV損壞或者不導通

控制器主控制板L6燈滅

檢查主控板7腳對11、12、13腳有無+、-3伏左右電壓,否則更換電流傳感器

 

 

檢查固態繼電器FV

FV的3、4腳有(you)直(zhi)流15V電(dian)壓,而323、325不(bu)通,須更(geng)換該(gai)繼(ji)電(dian)器(qi)

進相后主(zhu)電機停機

接入開關柜的KM11、KM13的輔助觸點359、361接觸不好

維(wei)修(xiu)該觸點

 

進(jin)相器投入進(jin)相瞬間外部空氣開關(guan)跳閘

更換大規格的空氣(qi)開關

進相后無(wu)效果

接入主控板的(de)電流(liu)傳(chuan)感器信號線錯(cuo)誤(wu)

電流傳感器從左到右TA1、TA2、TA3的信號線應分別對應與主控板的13、12、11腳

 

主控(kong)板的(de)撥碼開(kai)關在(zai)自檢(jian)位

撥碼開關撥至工作位

 

KM13吸(xi)合后KM11未釋放(時(shi)間繼電(dian)器KT11壞)

更換KT11時間繼電器

 

KM15沒有吸合

KM11的輔助觸點(dian)301、305接觸不良

維修該觸點

 

 

KM15線圈故障

更換KM15線圈

 

KM15主觸(chu)(chu)點接觸(chu)(chu)不良

更換KM15

 

主變(bian)壓器原邊開路

更換主變(bian)壓器(qi)

進相后主電機(ji)電流不減反(fan)增

同步(bu)電源相序錯誤(wu)

調換進相器內小變壓器TC上輸出6V、6V0電壓的兩線位置

 

電(dian)機(ji)轉速下降(jiang)(缺(que)相),自(zi)動退相

KM13主觸點(dian)接觸不良

維修該(gai)觸點

 

 

電機轉子(zi)線松(song)動,進相時的電流沖擊導致缺(que)相

檢(jian)查電機轉子線

進相(xiang)后主(zhu)電機電流擺動(dong)大

可(ke)控硅擊穿(chuan)

測量可控硅極間電阻(詳(xiang)細方法見調試部分(fen))

 

觸發板損壞

測量可控硅控制極與陰極之間應有0.2V以上的直流電壓信號,否則應檢查觸發板

 

主板(ban)的撥碼開關在自檢位

撥(bo)碼開關撥(bo)至工(gong)作位(wei)

 

電(dian)機(ji)轉子線(xian)松動

檢查電機轉子(zi)線

 

KM13采用節能型線圈時,線圈故障導致KM13進行瞬間來回釋放、吸合,導致主回路接觸不良

維修或更換KM13線圈





注意:進相器檢修不得在進相狀態下進行,發(fa)現問題(ti)應立即退相。

十二控制板檢(jian)修



現象

原因

對策

L1L2L3不循環閃爍,L6滅,其它各燈正常

轉子缺相

檢查接觸器KM2主觸頭是否損壞,若損壞,則維修觸頭或更換接觸器

電流傳感器器損壞

檢查電流傳感器是否有±2V以上的輸出信號,否則更換傳感器

主控板元器件損壞(huai)

依次更換IC210IC211

L1L2L3不周期性閃爍,其它各燈正常

主控(kong)板元器件損壞

依次更換IC210IC211IC205IC207

L6滅,其它各燈正常

主(zhu)控(kong)板元器件損壞

依次更換IC207IC209

L5滅,其它各燈正常

散熱器溫度檢測回路故障(zhang)

檢(jian)查(cha)溫度開關及其連(lian)線

L4L7L8全部或部分滅

電(dian)源(yuan)故(gu)障

1、檢查變壓器及控制板是否有±18V電源

2、更換相應的780578157915

F1-L1L6 F2-L1L6部分指示燈亮,主板各燈正常

觸發板元器(qi)件損壞

1、有一片ULN2004損壞,更換之

2、脈沖變壓器接觸不良,作相應處理

F1-L1L6 F2-L1L6指示燈全滅,主板各燈正常

觸發板元器件損壞

1、兩片ULN2004損壞,更換之

2、更換555芯片

觸發(fa)板無電源

1、檢查主板7815是否有虛焊

2、檢查觸發板19腳與主板6腳連接是否正常





十(shi)三注意事(shi)項

1、進相(xiang)(xiang)器檢修應在(zai)退相(xiang)(xiang)狀(zhuang)態下進行(xing),發現問題(ti)應立即退相(xiang)(xiang)。

2、嚴禁隨意帶(dai)電(dian)插拔控(kong)(kong)制板(ban),檢(jian)修(xiu)控(kong)(kong)制板(ban)時(shi),一定要把空開QF3打下來。

3、更換可(ke)控(kong)硅(gui)(gui)(gui)時應注意陰(yin)、陽極(ji)(ji)的(de)(de)方向(xiang),并(bing)壓緊(jin)散熱(re)器(壓力不要過(guo)大),裝上后擰緊(jin)所有螺絲(si),之后再(zai)檢測(ce)(ce)可(ke)控(kong)硅(gui)(gui)(gui)各(ge)極(ji)(ji)間的(de)(de)電阻情況(kuang)。若一只可(ke)控(kong)硅(gui)(gui)(gui)擊穿在柜體上直(zhi)接檢測(ce)(ce),同一相(xiang)的(de)(de)四個可(ke)控(kong)硅(gui)(gui)(gui)均顯示擊穿,此時應把該組(zu)可(ke)控(kong)硅(gui)(gui)(gui)間的(de)(de)聯接銅(tong)排(pai)拆掉再(zai)測(ce)(ce) 。

十四訂(ding)貨須知

1、提供電(dian)(dian)機型號、額定(ding)(ding)功(gong)率、定(ding)(ding)子電(dian)(dian)壓、定(ding)(ding)子電(dian)(dian)流、轉子電(dian)(dian)壓、轉子電(dian)(dian)流、額定(ding)(ding)功(gong)率因數。

2、提(ti)供(gong)電機拖動負載的(de)特征及負載率。

預知(zhi)TP系列無環流靜止式進相器的更多信息,請撥(bo)打襄(xiang)陽拓(tuo)邦電氣官網電話: 鄭經理17771133316或咨詢網站客服!!